Inspection
Inspection Details
Equipment ID
2741
2741
Inspection Date
6/21/2018
6/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Swett
Daniel Swett
Mechanic Name
Relief Valve Pressure
Slide
24
24
Governor Rope Pull
/640
/640
Door Closing Force
18
18
External ID
Location
Wohl Clinic
4950 Children's Place, St. Louis, MO
Phone: (314) 747-0740
4950 Children's Place, St. Louis, MO
Phone: (314) 747-0740
Owner
WUSM
660 S, Euclid, St. Louis, MO 63110
660 S, Euclid, St. Louis, MO 63110
Billing
Attn: WUSM
660 S, Euclid, , MO 63110
660 S, Euclid, , MO 63110
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.4 - Machine space | 100.5 | No | No | 101.5 HVAC not working in machine room. | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Emergency power existing but not tested. | 6/11/2020 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | 211.1(a)(3) Observed emergency light not working as required on battery backup. | 6/11/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Fire extinguisher out of date. | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2 way communication and emergency lighting not working when 110V is removed. | 6/9/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency power testing failed on this elevator | 6/9/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In-car alarm bell not ringing when 110V is removed. | 6/8/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | A17.1 1994 211.2 - Tripped limit board in down direction between 2-1 and went out of service during emergency power test. | 6/8/2023 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension cables undersized. | 5/23/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | cCar occasionally washes out on emergency power, however it does recover. | 5/23/2024 |