Inspection
Inspection Details
Equipment ID
19770
19770
Inspection Date
9/11/2020
9/11/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Steve Wiseman
Steve Wiseman
Relief Valve Pressure
340
340
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
705cfcbd-ddd4-4ef7-a3ce-b2e646522eb6
705cfcbd-ddd4-4ef7-a3ce-b2e646522eb6
Location
Celebration Cove 3
80 CELEBRATION CV, BRANSON, MO
Phone: (816) 805-1798
80 CELEBRATION CV, BRANSON, MO
Phone: (816) 805-1798
Owner
Celebration Cove POA
106 CELEBRATION CV UNIT 214, BRANSON, MO 65616-7983
106 CELEBRATION CV UNIT 214, BRANSON, MO 65616-7983
Billing
Attn: Celebration Cove
106 CELEBRATION CV UNIT 214, BRANSON, MO 65616-7983
106 CELEBRATION CV UNIT 214, BRANSON, MO 65616-7983
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | Remove the added photo equipment from the machine room | 12/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone | 12/17/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair or replace the emergency phone as it still does not work. There is no dial tone. | 9/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.1 Examination and Maintenance of Packing Glands and Seals | Yes | No | Replace the packing as it is leaking excessively | 10/16/2020 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | No | No | Repair or replace the emergency phone as there is no dial tone | 12/17/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 12/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | have the expired fire extinguisher re-certified | 1/27/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all the stored materials from the machine room. | 1/27/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Have the fire extinguisher re-certified | 10/18/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Remove all the stored materials from the elevator machine room. | 10/18/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean up the oil spill on the pit floor | 10/18/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. | 10/18/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as the incoming line is dead, it has no dial tone | 1/30/2026 |