Inspection
Inspection Details
Equipment ID
15160
15160
Inspection Date
9/1/2020
9/1/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
Slide
14
14
Governor Rope Pull
40/180
40/180
Door Closing Force
21
21
External ID
6267c71d-b5aa-4310-a5da-73e1020fa4e8
6267c71d-b5aa-4310-a5da-73e1020fa4e8
Location
The Saum & Hutcheson Arms Apartments
1919 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 685-1130
1919 S GRAND BLVD, SAINT LOUIS, MO
Phone: (314) 685-1130
Owner
Attn: Revival STL Construction, LLC
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Pit light shall work. | 3/22/2019 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Provide adequate machine room lighting. | 3/22/2019 | ||
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Phase 2 fire service shall work. | 10/4/2018 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | Unable to test the emergency lighting. | 3/22/2019 | ||
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Phase 2 fire service shall work. | 11/13/2018 | |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Phase 2 fire service shall be operational. | 1/15/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean the pit. The pit shall be kept clean. | 11/1/2019 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit shall be kept clean. | 9/15/2020 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | Provide MCP | 11/1/2021 | ||
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | Post Phase I instructions near f/f switch | 11/1/2021 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Phase II halo worn and unreadable | 11/1/2021 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Clean pit | 11/1/2021 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Sheave seal worn and leaking, repair as needled | 11/1/2021 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Need to replace defective hoist cables due to excessive rouge & diameter reduction. Re-inspection required in 90 days | 2/26/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Need to replace missing door gibbs on the 1st, 4th & 8th floors |