Inspection
Inspection Details
Equipment ID
6760
6760
Inspection Date
9/1/2020
9/1/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
22
22
External ID
e753501e-cb58-4e8d-8d13-f35b6cf0e45e
e753501e-cb58-4e8d-8d13-f35b6cf0e45e
Location
Hutcheson Arms Apts
2107 S GRAND BLVD, SAINT LOUIS, MO
Phone: (000) 000-0000
2107 S GRAND BLVD, SAINT LOUIS, MO
Phone: (000) 000-0000
Owner
Attn: Revival STL Construction, LLC
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Pit shall be clean and dry | 3/25/2019 |
| conversion | conversion | n/a | No | No | 5 CWT roller guides need to be replaced | 3/25/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Remove the water from the pit. | 3/25/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Car emergency lighting shall work. | 3/25/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.19 - Guide rails fastening and equipment | 8.11.2.1.3(y) | No | No | Replace the car and counterweight roller guides where needed. | 11/1/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.26.8 | Yes | No | 2.19 - Unintended movement does not work in either direction. | 5/1/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean and dry. | 12/1/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 12/18/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Repair receptacles in machine room. | 12/1/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | Repair ventilation in machine room. | 12/1/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone not working | 9/30/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Pit to be clean and dry | 10/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate | 10/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Repair receptacles in machine room | 10/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | Provide machine room ventilation | 10/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Clean car top | 10/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | Clean machine room | 9/30/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Out of adjustment | 9/30/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Guard bulbs in machine room | 10/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Light hanging by wires | 10/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.11.2.1.3(w) | No | No | Hoist way doors missing guides | 10/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Door frame broken, replace | 10/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Machine room door not self locking | 10/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Machine room door to be self closing | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide MCP | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 12/21/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Yes | No | Pit needs to be clean & dry | 12/21/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | Need to post current certificate | 12/21/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.8.1 Electrical Equipment and Wiring | Yes | No | Repair receptacles in machine room | 12/21/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | Yes | No | Provide machine room ventilation | 12/21/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | Yes | No | Need to clean car top | 12/21/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | Yes | No | Need to clean machine room. Re-inspection required | 12/21/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Out of adjustment. Re-inspection required | 12/21/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Door frame broken, need to be replaced | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door to be self closing and self locking | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | Emergency lighting is not working. Re-inspection required | 1/16/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Bell and Phone not Functioning (Red Tag) | Yes | Yes | Emergency phone is not working. Re-inspection required. Red-tagged unit | 1/16/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | Yes | Alarm bell is not working. Re-inspection required. Red-tagged unit | 1/16/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has water running on floor, needs to be cleaned | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Yes | No | Water flowing into pit, provide means to abate. | 10/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.6 Sump Pump Covers | Yes | No | Sump pump cover not in place, make so. | 10/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Yes | No | Sump pump currently has a garden hose leading out of sump hole through the pit. Through the next car pit, out a hole punched into the Hoistway wall.Remove hose, provide sump to drain correctly per design. Seal hole in hoistway wall | 10/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Yes | No | Observed sump pump improperly wired, make per code. | 10/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Yes | No | Provide current year MCP. | 10/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Door restrictor not working. Repair as needed. | 10/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Pit Light not working | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Electrical box on pit wall missing cover and wires are exposed | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 8.1 - Machinery space access, lighting, receptacle, and condition | 8.6.8.14 Cleaning | No | No | Machine needs cleaned | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post Current Operating Certificate | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | Provide current Maintenance Control Program | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Machine Room door shall be self locking | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.1(h) Call Cancel Button (Re-Inspection) | Yes | No | FEO Phase 2 does not override 11th floor cutout keyswitch 2.27.3.3.1(i) |