Inspection
Inspection Details
Equipment ID
13755
13755
Inspection Date
9/2/2020
9/2/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Jason Bock
Jason Bock
Relief Valve Pressure
Slide
16"
16"
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
9c5797db-b21f-4083-b180-e9ac7baf7340
9c5797db-b21f-4083-b180-e9ac7baf7340
Location
EC & S Partners, LLC
2801 LOCUST ST, SAINT LOUIS, MO
Phone: (314) 361-6075
2801 LOCUST ST, SAINT LOUIS, MO
Phone: (314) 361-6075
Owner
Attn: Cathy Strobel
EC & S Partners, LLC
2801 Locust St, St. Louis, MO 63103
Phone: (314) 570-9218
Email: cathystrobel@neostl.com
EC & S Partners, LLC
2801 Locust St, St. Louis, MO 63103
Phone: (314) 570-9218
Email: cathystrobel@neostl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide a current tested fire extinguisher in the elevator machine room. Fire extinguisher is expired. | 11/7/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Existing pit light shall work. | 11/7/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | No | No | Provide braille tactile plate on door frame at the 5th floor. | 11/7/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car ADA telephone shall operate on auxiliary power. | 12/5/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | The hoist cables shall not rub on the machine room cable slot. Determine the cause and take corrective action. | 9/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/15/2020 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 2.19.2 | No | Yes | The emergency brake (rope gripper) failed to stop the motion of the car on unintended movement with 125% of rated load within 48". - Unit Red Tagged | 7/2/2020 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | No | Unintended movement shall be tested with an empty car. - Re-Inspection Required | 7/2/2020 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.4 | No | No | 2.4.5 - A data plate permanently and securely attached shall be provided in the pit, in the vicinity of the counterweight buffer, indicating the maximum designed counterweight runby. | 7/2/2020 |
| A17.1-2016 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 8.11.2.1.5(c) | No | No | 8.11.2.3.3 - The car buffer shall be tested at rated speed with rated load. The counterweight buffer shall be tested at rated speed with an empty car. - Re-Inspection Required | 7/2/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc) | No | No | The hoist cables shall not rub on the machine room cable slot. Determine the cause and take corrective action. | 9/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/15/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unintended movement shall be tested with an empty car. - Re-Inspection Required | 9/2/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.5 Counterweight Runby Data Plate | No | No | 2.4.5 - A data plate permanently and securely attached shall be provided in the pit, in the vicinity of the counterweight buffer, indicating the maximum designed counterweight runby. | 9/15/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | 8.11.2.3.3 - The car buffer shall be tested at rated speed with rated load. The counterweight buffer shall be tested at rated speed with an empty car. - Re-Inspection Required | 9/2/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Unintended movement in both directions shall be tested. *NOTE* Removed red tag only per Gus Guadamuz. Unintended movement down with 100% capacity was 46.5". Gus Guadamuz agreed to release unit based upon a maximum load of 10 people only. | 9/2/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 7/14/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current tested and tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 9/21/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | The A/C in the machine room is in need of repair. Machine rooms shall be provided with natural or mechanical means to keep the ambient air temperature and humidity in the range specified by the equipment manufacturer. | 9/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The following needs reinspect to complete Cat 5: car buffer,125% brake, car safety, unintended, ascending, Phase I and II. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean down the hoistway. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean the pit. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Provide safe and convenient access to the elevator machine room.( beam blocking ladder) | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide current year tested fire extinguisher in the elevator machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Observed black mold on the ceiling, top floor. Abate. |