Inspection
Inspection Details
Equipment ID
17696
17696
Inspection Date
8/27/2020
8/27/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
10"
10"
Governor Rope Pull
60/350
60/350
Door Closing Force
25
25
External ID
464b1ad6-21dc-412a-80f0-1be76eea9d5b
464b1ad6-21dc-412a-80f0-1be76eea9d5b
Location
Delmar Loop Apartments
5621 Delmar Blvd, St. Louis, MO
Phone: (000) 000-0000
5621 Delmar Blvd, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Delmar Loop Apartments
c/o STL Apartments
1507 Hwy A, Wentzville, MO 63385
Phone: (000) 000-0000
Email: steve.bross@etrailer.com
c/o STL Apartments
1507 Hwy A, Wentzville, MO 63385
Phone: (000) 000-0000
Email: steve.bross@etrailer.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | In car emergency lights shall work. | 1/2/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency bell and phone shall work. | 10/16/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Provide safe and convenient access to the elevator machine room. Wooden stairs leading to machine room are worn and unsafe. | 2/28/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit sump pump shall work. | 2/28/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove fluids from the pit. The pit shall be kept dry. | 2/28/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The doors stopped working during the inspection. All category 5 and annual inspection items have been completed with the exception of fire service. Fire service shall be tested as part of the category 5 annual inspection | 10/8/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency telephone shall be operational. | 8/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 8/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The car safety edge re-opening device does not work properly when car door is a foot from fully closing. | 8/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Rescue plan is missing. (This item is for notification purposes for future violation in 2022) | 2/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 10/4/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide code compliant machine room lighting. The illumination the machine room shall be not less than 10 foot-candles at the floor level. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Remove the bag covering the smoke detector in the machine room. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/29/2023 |