Inspection
Inspection Details
Equipment ID
6389
6389
Inspection Date
9/4/2020
9/4/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
560
560
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
7ab11902-ea44-4974-8fd2-7025bde98dbc
7ab11902-ea44-4974-8fd2-7025bde98dbc
Location
St. Louis Technology Center
587 JAMES S MCDONNELL BLVD, HAZELWOOD, MO
Phone: (314) 989-1011
587 JAMES S MCDONNELL BLVD, HAZELWOOD, MO
Phone: (314) 989-1011
Owner
Attn: Refinitiv
Refinitiv
587 James McDonnell Blvd, Hazelwood, MO 63042
Phone: (000) 000-0000
Email: facundo.izquierdo@cbre.com
Refinitiv
587 James McDonnell Blvd, Hazelwood, MO 63042
Phone: (000) 000-0000
Email: facundo.izquierdo@cbre.com
Billing
Attn: CBRE Managed Services, Inc
CBRE Managed Services, Inc
2100 Ross Avenue, Ste 1600, Dallas, TX 75201
Phone: (000) 000-0000
Email: facundo.izquierdo@cbre.com
CBRE Managed Services, Inc
2100 Ross Avenue, Ste 1600, Dallas, TX 75201
Phone: (000) 000-0000
Email: facundo.izquierdo@cbre.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 9/4/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Maintenance control program shall include written procedures for inspections and tests located on site. | 11/3/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current state operating certificate located in machine room. | 11/3/2020 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency power needs to be tested, generators will be tested on bldg on 3/5/22. | 3/5/2022 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV needs to be tested in or less than 90 days | 3/5/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV needs to be tested on or before 4/28/22. Re-inspection required | 8/25/2022 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor is not working. Re-inspection required | 8/19/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 12/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing of emergency generator power operation needs to be scheduled to complete inspection. Re-inspection required | 8/19/2023 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor is not working. Re-inspection required | 8/28/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room. | 12/18/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room | 12/18/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency generator power. Re-inspection required | 2/8/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 12/11/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Perform form the emergency power testing to complete the Cat 1 tests. | 12/11/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.5 Illuminated Visual Signal | Yes | No | Failed Cat 1 firefighters service test. Door hold button did not work, only elevator in building, needs repaired. Re-inspection required |