Inspection
Inspection Details
Equipment ID
7931
7931
Inspection Date
9/4/2020
9/4/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
John Carpentier, Sr.
John Carpentier, Sr.
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
5043c633-9b89-44f0-bf85-4030944b8352
5043c633-9b89-44f0-bf85-4030944b8352
Location
Parkway Towers Office Bldg
225 S MERAMEC AVE, CLAYTON, MO
Phone: (314) 880-7676
225 S MERAMEC AVE, CLAYTON, MO
Phone: (314) 880-7676
Owner
Attn: BMO-I Parkway Towers, LLC
BMO-I Parkway Towers, LLC
600 Emerson Rd, Ste 210, Creve Coeur, MO 63141
Phone: (000) 000-0000
BMO-I Parkway Towers, LLC
600 Emerson Rd, Ste 210, Creve Coeur, MO 63141
Phone: (000) 000-0000
Billing
Attn: BMO-I Parkway Towers, LLC
BMO-I Parkway Towers, LLC
225-235 S Meramec Ave, Creve Coeur, MO 63105
Phone: (000) 000-0000
Email: sashcraft@intcre.com
BMO-I Parkway Towers, LLC
225-235 S Meramec Ave, Creve Coeur, MO 63105
Phone: (000) 000-0000
Email: sashcraft@intcre.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | x | Restricted opening inoperative, repair. | 9/30/2019 | |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | No audible signal on Phase I return. | 1/30/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | x | Repair car door restrictor. | 1/30/2020 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | x | Door restrictor works intermittently. Repair or replace. | 10/1/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Provide pit bucket for oil collection. | 9/17/2020 | ||
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | Provide feeder location on main line disconnect (NEC620.51) | 7/31/2023 | |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | x | Provide feeder location on 110v. disconnect(NEC620.51). | 7/31/2023 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | x | Provide pit GFCI outlet to work properly (NEC620). | 7/31/2023 | |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | x | Provide existing climate control in the elevator machine room to work properly. | 7/31/2023 | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.7.1 | x | Seal all machine room wall and ceiling penetrations. | 7/31/2023 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x | Existing pipes over the elevator equipment are leaking repair as needed. | 7/31/2023 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | x | Existing pipes to be covered to prevent future leaks/condensation from the elevator equipment. | 7/31/2023 | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | Provide Phase I emergency recall operations by Fire Alarm Initiating Devices (FAID) | 7/31/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Clean car top | |||
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | Seal top of hoistway, water entering. |