Inspection
Inspection Details
Equipment ID
8009
8009
Inspection Date
9/4/2020
9/4/2020
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Jonathan Harrison
Jonathan Harrison
Relief Valve Pressure
Slide
Type C - NA
Type C - NA
Governor Rope Pull
50/620
50/620
Door Closing Force
26
26
External ID
2b734c57-f1de-4844-81dd-bf5a6aa26d9b
2b734c57-f1de-4844-81dd-bf5a6aa26d9b
Location
Enterprise Center
1401 CLARK AVE, SAINT LOUIS, MO
Phone: (314) 589-5982
1401 CLARK AVE, SAINT LOUIS, MO
Phone: (314) 589-5982
Owner
Attn: Doug Waugh
Enterprise Center
1401 CLARK AVE, SAINT LOUIS, MO 63103
Phone: (314) 589-5982
Email: dwaugh@enterprisecenter.com
Enterprise Center
1401 CLARK AVE, SAINT LOUIS, MO 63103
Phone: (314) 589-5982
Email: dwaugh@enterprisecenter.com
Billing
Attn: Doug Waugh
Enterprise Center
1401 CLARK AVE, SAINT LOUIS, MO 63103
Phone: (314) 589-5982
Email: dwaugh@enterprisecenter.com
Enterprise Center
1401 CLARK AVE, SAINT LOUIS, MO 63103
Phone: (314) 589-5982
Email: dwaugh@enterprisecenter.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair gaps on car doors over 3/8" wide | 1/29/2026 |
| conversion | conversion | conversion - reinspect | Yes | No | Cab emergency lights do not work. | 3/22/2019 |
| conversion | conversion | n/a | No | No | Traction machine worm seal leaking oil | 1/29/2026 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency alarm bell and light shall work. | 9/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Yes | No | All wireway and electrical devices covers shall be installed. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Yes | No | Temporary wiring shall be removed. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | The penetrations in the hoistway shall be sealed with approved solid material. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.5 Counterweight Runby Data Plate | Yes | No | A counterweight runby sign shall be provided in the pit. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | A standby power test shall be performed. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | The new smoke installation shall be completed and tested. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | Yes | No | An identification number or letter shall be provided adjacent to or on every elevator entrance at the designated level, and be a minimum of 3 inches in height. | 10/9/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Provide minimum c/w run by. | 8/2/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired | 1/29/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | Yes | No | The rope shall be shortend. Unit was red tagged. | 5/1/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete. 100% set, unintended motion, and 125% run/hold remain to be tested. | 5/1/2026 |