Inspection
Inspection Details
Equipment ID
6489
6489
Inspection Date
9/15/2020
9/15/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
John Ryan
John Ryan
Relief Valve Pressure
220/390
220/390
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
53654c66-56de-4657-af20-3ca82d2db82d
53654c66-56de-4657-af20-3ca82d2db82d
Location
Holiday Inn Express
4630 LINDELL BLVD, SAINT LOUIS, MO
Phone: (314) 361-4900
4630 LINDELL BLVD, SAINT LOUIS, MO
Phone: (314) 361-4900
Owner
Attn: UNK
Garrison St. Louis OP Co. LLC
1290 AVENUE OF THE AMERICAS STE 916, NEW YORK, NY 10019
Phone: (000) 000-0000
Garrison St. Louis OP Co. LLC
1290 AVENUE OF THE AMERICAS STE 916, NEW YORK, NY 10019
Phone: (000) 000-0000
Billing
Attn: Holiday Inn Express
Holiday Inn Express
4630 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (314) 361-4900
Email: PLANDA@HIEXPRESSCWE.COM
Holiday Inn Express
4630 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (314) 361-4900
Email: PLANDA@HIEXPRESSCWE.COM
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 12/1/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit and the hoistway shall be kept clean. | 12/1/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The machine room shall be kept clean. Equipment and materials not necessary for the operation or maintenance of the elevator shall not be stored in the machine room. | 10/1/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Clean the pit. | 10/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top and hoistway are in need of a clean down. Clean the car top and hoistway. | 10/1/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The emergency lighting shall be operational. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit and the hoistway shall be cleaned. | 10/1/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | The top of the car shall be cleaned. | 10/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Door close button is activated at all times and creating issues with Phase 2 fire service. Repair as needed. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | The machine room shall be cleaned out and all non-elevator related items shall be removed from the elevator machine room. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/1/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/22/2024 |