Inspection
Inspection Details
Equipment ID
13321
13321
Inspection Date
9/9/2020
9/9/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Brent Davis
Brent Davis
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
25
25
External ID
efc0f095-0cbb-4f46-8627-9a61bb965e6d
efc0f095-0cbb-4f46-8627-9a61bb965e6d
Location
Homer Phillips
2601 WHITTIER ST, SAINT LOUIS, MO
Phone: (314) 535-3223
2601 WHITTIER ST, SAINT LOUIS, MO
Phone: (314) 535-3223
Owner
Attn: EPV Dignity House LLC
EPV Dignity House LLC
125 John Roberts Rd #12, South Portland, ME 04106
Phone: (616) 340-3753
EPV Dignity House LLC
125 John Roberts Rd #12, South Portland, ME 04106
Phone: (616) 340-3753
Billing
Attn: Homer Philliips Dignity House II
Homer Philliips Dignity House II
2601 Whittier St, St. Louis, MO 63113
Phone: (000) 000-0000
Homer Philliips Dignity House II
2601 Whittier St, St. Louis, MO 63113
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Phase Ii does not work | 8/30/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Phase I light and buzzer not working | 8/30/2018 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) | Yes | Yes | Repair firefighters service phase II so that it operates as intended. Hold does not work. Did not red tag unit. Reinspect only. | 8/2/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | No | No | Fireman's light and audible needs to work. | 5/13/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) | Yes | Yes | Phase 2 is not working, hold does not work, fireman's in car light and buzzer not working. Must be repaired within 30 days, reinspected by October 9th or unit will be red tagged. | 10/13/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not have 2-way communication. | 10/13/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Maintenance control program shall include current records of maintenance performed. | 10/23/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | 2/11/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control records. | 11/15/2021 |
| A17.1-1996 : Elevators | 2.18 - Traction drive machines | 1001.2(b)(16) | Yes | No | Drive sheave seals and worm shaft seals are worn and leaking. Repair as needed. | 11/15/2021 |
| A17.1-1996 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 1206.2(c) | No | No | Clean oil from car top, including car fan and ceiling fixtures. | 11/15/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean pit. | 11/15/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency lights and alarm bell do not work. | 11/15/2021 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | Yes | No | Repair door detector, currently working off light/bell 110V circuit. When power is removed, it does not work. | 11/15/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work, pushing button = nothing. | 9/2/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | phase I and II not working |