Inspection
Inspection Details
Equipment ID
21086
21086
Inspection Date
9/11/2020
9/11/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
f2f7ce83-ba6a-4775-979a-2498df36eba1
f2f7ce83-ba6a-4775-979a-2498df36eba1
Location
Brookdale West County Senior Living
785 HENRY AVE, BALLWIN, MO
Phone: (636) 866-1211
785 HENRY AVE, BALLWIN, MO
Phone: (636) 866-1211
Owner
Brookdale West County
785 HENRY AVE, BALLWIN, MO 63011-2736
785 HENRY AVE, BALLWIN, MO 63011-2736
Billing
Attn: Brookdale West County
785 HENRY AVE, BALLWIN, MO 63011-2736
785 HENRY AVE, BALLWIN, MO 63011-2736
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | No current maintenance records on site. | 4/4/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car appears dead, needs to be repaired. Re-inspection required | 12/7/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unable to access Phase II fire service controls in car. All fire service needs to be tested. Re-inspection required | 12/7/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to clean pit | 4/4/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Need to clean cartop | 4/4/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. RE-inspection required | 3/28/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unable t access Phase I fire service controls in car. All fire service needs to be tested. Re-inspection required | 3/28/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 4/4/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 Gland Packings and Seals | No | No | Packing is worn and leaking, repair as needed. | 4/4/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean the pit (oil). | 4/4/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall give proper location message. No location message given. | 3/17/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/17/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and related on-site documentaion shall be provided in the machine room. Missing PM/repair/callback logs for 2023, 2024, & 2025. | 3/17/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | No | No | Replace missing door gibs on hoistway doors. | 3/17/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service testing must be documented monthly. | 3/17/2026 |