Inspection
Inspection Details
Equipment ID
8106
8106
Inspection Date
9/21/2020
9/21/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
c5222fec-7d09-4ea8-bef7-f6e0bab49a3d
c5222fec-7d09-4ea8-bef7-f6e0bab49a3d
Location
GM Truck Assembly Plant
1500 HIGHWAY A, WENTZVILLE, MO
Phone: (314) 226-8291
Email: demetrius.bell@gm.com
1500 HIGHWAY A, WENTZVILLE, MO
Phone: (314) 226-8291
Email: demetrius.bell@gm.com
Owner
Attn: David Heubel
General Motors Company
1500 Hwy A, Wentzville, MO 63385
Phone: (000) 000-0000
Email: david.heubel@gm.com
General Motors Company
1500 Hwy A, Wentzville, MO 63385
Phone: (000) 000-0000
Email: david.heubel@gm.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Repair machine room lighting. | 8/20/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | No | No | Phase II sign missing in car. | 8/20/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Cover all uncovered electrical boxes. | 9/4/2020 |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | No | No | Repair lower panel section of bi-parting doors at both lower landings, care side. Door skin separating from trucking sill. | 9/4/2020 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Repair or replace cab emergency lighting. | 9/21/2020 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Repair machine room lighting. | 9/4/2020 |
| A17.1-1996 : Elevators | 2.33 - Tanks | 1206.5b | No | No | Remove scavenger pump from pit. The amount of oil leakage cannot be monitored. | 1/18/2022 |
| A17.1-1996 : Elevators | 2.33 - Tanks | 1206.5b | No | No | Remove scavenger pump from pit. The amount of oil leakage cannot be monitored. | 11/30/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit floor is flooded with water, pit should be kept clean & dry. | 11/30/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete because elevator broke down, only thing that was completed was fire service. Re-inspection required | 6/9/2023 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.1 Examination and Maintenance | Yes | Yes | Packing is bad. Piston is worn past holding the packing, replace jack | 10/25/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 11/9/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | All phases of fire service and all initiating devices shall be tested. | 11/9/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency power operation shall be tested. | 11/9/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power generator testing shall be performed. Re-inspection required |