Inspection
Inspection Details
Equipment ID
24143
24143
Inspection Date
9/23/2020
9/23/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Jeffrey Krug
Jeffrey Krug
Mechanic Name
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
n/a
n/a
External ID
f5003d42-a238-4d71-bdc9-204385fc6a59
f5003d42-a238-4d71-bdc9-204385fc6a59
Location
Plaza on West Pine Phase II
3940 W PINE BLVD, SAINT LOUIS, MO
3940 W PINE BLVD, SAINT LOUIS, MO
Owner
Attn: UNK
E-404 Construction
148 CHESTERFIELD INDUSTRIAL BLVD STE G, CHESTERFIELD, MO 63005
Phone: (000) 000-0000
E-404 Construction
148 CHESTERFIELD INDUSTRIAL BLVD STE G, CHESTERFIELD, MO 63005
Phone: (000) 000-0000
Billing
Attn: UNK
E-404 Construction
148 CHESTERFIELD INDUSTRIAL BLVD STE G, CHESTERFIELD, MO 63005
Phone: (000) 000-0000
Email: deanna@e404lllc.com
E-404 Construction
148 CHESTERFIELD INDUSTRIAL BLVD STE G, CHESTERFIELD, MO 63005
Phone: (000) 000-0000
Email: deanna@e404lllc.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 (Re-Inspection) | Yes | No | Control room illumination shall be 19 foot candles. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Hoistway shall be as near vertical as possible. Shall be capable of holding 150#/sq ft without deformation. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Seal all hoistway penetration to maintain fire rating. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | NEC Secure conduit at top of hoistway. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.1.1 | Yes | No | Install self closing, self locking door on controller disconnect room. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.18 - Traction drive machines | 2.24 | Yes | No | Auxillary contacted on shunt and disconnect. 2.11 is not an Item Option and needs to be added. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.16.8 | Yes | No | Test standby power operation. | 8/10/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Telephone in car doesn't work. Will not activate | 10/22/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Telephone in car doesn't work. Phone line dead to elevator controller | 9/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The emergency alarm button and door open button are missing their labels and braille. Required signs and data plates that are damaged or missing shall be repaired or replaced | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written Maintenance Control Program, provided by the person(s) maintaining the equipment, shall be in place to maintain the equipment in compliance with the requirements of Section 8.6. |