Inspection
Inspection Details
Equipment ID
8829
8829
Inspection Date
9/23/2020
9/23/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Kirk Luttrell
Kirk Luttrell
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
1cab75d3-c24e-48af-acc2-4a94552f8f3a
1cab75d3-c24e-48af-acc2-4a94552f8f3a
Location
Wesley Senior Towers
1002 FRANCIS ST, SAINT JOSEPH, MO
Phone: (816) 233-4255
1002 FRANCIS ST, SAINT JOSEPH, MO
Phone: (816) 233-4255
Owner
Attn: Wesley Senior Towers
Wesley Senior Towers
220 NW Executive Way, LEES SUMMIT, MO 64063
Phone: (816) 246-9220
Email: mallory@fulsonhousing.com
Wesley Senior Towers
220 NW Executive Way, LEES SUMMIT, MO 64063
Phone: (816) 246-9220
Email: mallory@fulsonhousing.com
Billing
Attn: Wesley Senior Towers
Wesley Senior Towers
220 NW Executive Way, LEES SUMMIT, MO 64063
Phone: (816) 246-9220
Email: wesley@fulsonhousing.com
Wesley Senior Towers
220 NW Executive Way, LEES SUMMIT, MO 64063
Phone: (816) 246-9220
Email: wesley@fulsonhousing.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency light and bell do not operate. | 6/4/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.16.8 | Yes | No | Driving machine does not safely lower and stop elevator with 125% of rated load on the elevator. | 9/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Fire hat inside elevator does not flash when machine room fire alarm initiating device is activated. | 9/23/2020 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.19.2 | Yes | Yes | Perform no load safety test. Elevator is past due for annual safety testing. | 9/23/2020 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.20.2 | Yes | No | Test tripping speed of governor and forces of pull thru | 7/19/2021 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | No | Test unintended motion in down direction with 125% of rated load | 7/19/2021 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.6.4.20.10 | Yes | No | Perform 125% brake test | 7/19/2021 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | Yes | Perform full load safety test | 7/19/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | Mark governor with identification number #2 | 8/10/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(d)(1) | No | No | Post emergency evacuation of passengers procedure in machine room | 8/10/2021 |
| A17.1-2016 : Elevators | 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection | 8.6.4.20.11 (Re-Inspection) | Yes | Yes | Unintend motion down test exceeded 48 inches. Elevator car sill stopped 76 inches below the landing sill. | 8/9/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Install dust covers on all 12 hoistway door hangers. Dustcovers are laying on top of the elevator. | 6/28/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | DOOR CLOSING FORCE IS >30 | 8/14/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | REPLACE BAD HOIST ROPES | 4/14/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | PROVIDE A SAFE MEANS FOR ENTERING & EXITING THE ROOF FROM THE HATCH LADDER | 4/14/2026 |
| A17.1-2016 : Elevators | 2.1 - Access to machine space | 2.7.3.1 | No | No | 2.7.3.2.1 A STAIRWAY WITH A SWING DOOR AND PLATFORM AT THE TOP LEVEL, CONFORMING TO 2.7.3.3 SHALL BE PROVIDED FROM THE TOP FLOOR OF THE BUILDING TO THE ROOF LEVEL. HATCH COVERS, AS A MEANS OF ACCESS TO ROOFS , SHALL NOT BE PERMITTED |