Inspection
Inspection Details
Equipment ID
9157
9157
Inspection Date
9/18/2020
9/18/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
360
360
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
5abdb9be-55a3-4f59-a908-06b2f78ed4ef
5abdb9be-55a3-4f59-a908-06b2f78ed4ef
Location
Park 44 Apartments
4444 W PINE BLVD, SAINT LOUIS, MO
Phone: (314) 371-3545
4444 W PINE BLVD, SAINT LOUIS, MO
Phone: (314) 371-3545
Owner
Attn: Banner Property Management, LLC
Banner Property Management, LLC
500 SKOKIE BLVD STE 600, NORTHBROOK, IL 60062
Phone: (000) 000-0000
Banner Property Management, LLC
500 SKOKIE BLVD STE 600, NORTHBROOK, IL 60062
Phone: (000) 000-0000
Billing
Attn: Banner Property Management LLC
Banner Property Management, LLC
PO BOX 7682, MERRIFIELD, VA 22116
Phone: (000) 000-0000
Email: Park44.manager@bannerApartments.com
Banner Property Management, LLC
PO BOX 7682, MERRIFIELD, VA 22116
Phone: (000) 000-0000
Email: Park44.manager@bannerApartments.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Clean oil from elevator pit. | 11/25/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean elevator pit. | 4/29/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written maintenance control program shall be kept on site for each elevator. | 11/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Scavenger pumps that do not record the amount of oil returned to the hydraulic tank cannot be installed. Either install recordable scavenger pump or limit the amount of oil stored in the pit to 5 gallons. | 11/28/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the elevator machine room | 11/28/2022 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV needs to be tested in 90 days or less | 5/6/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil from elevator pit | 11/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Scavenger pump must be removed, cannot log amount of oil loss from packing gland | 11/28/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Provide cover over sump pump hole | 12/8/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean & dry, need to clean pit & prevent sump pump from spraying back into pit | 12/8/2022 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 204.7 | No | No | Repair nonworking cartop light | 12/8/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be kept in the machine room | 12/8/2022 |
| A17.1-2016 : Elevators | 1.13 - Emergency exit | 2.14.1.5 | Yes | No | Drop ceiling does not allow access to emergency exit. Take corrective action as needed. | 1/13/2025 |
| A17.1-2016 : Elevators | 1.13 - Emergency exit | 2.14.1.5 | Yes | No | Drop ceiling does not allow access to emergency exit. Take corrective action as needed. Note: Car top emergency exit panel opens up to ceiling panel release latch. However, the whole back ceiling panel drops down for emergency exit, and the other ceiling panel release latch on the other end is under the car top with no access to it. Need to correct problem or apply for variance. | 2/18/2025 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 10/28/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit light does not work. | 10/28/2025 |