Inspection
Inspection Details
Equipment ID
1886
1886
Inspection Date
10/1/2020
10/1/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Brian Heine
Brian Heine
Relief Valve Pressure
Slide
Soft Set
Soft Set
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
7aa65dc4-7256-4ee2-8f2c-bd481160ad6b
7aa65dc4-7256-4ee2-8f2c-bd481160ad6b
Location
Courtyard by Marriott
400 Broadway Street, CAPE GIRARDEAU, MO
Phone: (573) 579-1901
400 Broadway Street, CAPE GIRARDEAU, MO
Phone: (573) 579-1901
Owner
Attn: UNK
H & H Center Property, LLC
1610 N. Kingshighway, Ste 301, CAPE GIRARDEAU, MO 63701
Phone: (573) 579-1901
Email: patty.schaefer@maysoncapital.com
H & H Center Property, LLC
1610 N. Kingshighway, Ste 301, CAPE GIRARDEAU, MO 63701
Phone: (573) 579-1901
Email: patty.schaefer@maysoncapital.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Complete fire service recall on smoke detectors, shunt trips, and heat detectors. | 9/20/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Label disconnects with feeder panel, location, number, and breaker numbers. | 9/20/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Seal all penetrations and voids in the hoistway. | 9/20/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Need to test emergency light. | 9/20/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Machine room railing system shall be completed. | 9/20/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Flooring in the cab shall be installed. | 9/20/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Need pit lighting, light switch, caution signage, and pit door signage. | 9/20/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | A code compliant fire extinguisher is required in the machine room. | 9/20/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Need to test emergency alarm and phone. | 9/20/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | All emergency fire service features shall be tested, including smoke detectors, heat detectors, and shunt trip disconnect. | 10/5/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate. | 8/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP. | 8/26/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 3/15/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 4/16/2021 |