Inspection
Inspection Details
Equipment ID
8894
8894
Inspection Date
9/22/2020
9/22/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
2a2aed98-587d-4d96-9180-0cf4ef96dc33
2a2aed98-587d-4d96-9180-0cf4ef96dc33
Location
Clayton Corporate Park Management Company
500 CORPORATE PARK DR, CLAYTON, MO
Phone: (314) 267-6881
500 CORPORATE PARK DR, CLAYTON, MO
Phone: (314) 267-6881
Owner
Clayton Corporate Park Management Company
500 CORPORATE PARK DR, CLAYTON, MO 63105-4202
500 CORPORATE PARK DR, CLAYTON, MO 63105-4202
Billing
Attn: Clayton Corporate Park Management Company
500 CORPORATE PARK DR, CLAYTON, MO 63105-4202
500 CORPORATE PARK DR, CLAYTON, MO 63105-4202
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Written maintenance control program shall be kept on site for each elevator. | 12/18/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1993), as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 10/31/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | The elevator has two large holes 2’ by 4’ cut into the back of the hoistway. The hoistway shall be repaired to be enclosed at its full length per the Missouri Minimum Standard. | 10/1/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 10/31/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Elevator has emergency power selector switch at main lobby landing. Facilities manager says elevator is not on emergency power. Either provide documentation that elevator is not on emergency power and remove selector switch, or test elevator for operation on emergency power. Re-inspection required | 10/1/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to (A17.1 1993) as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 10/1/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | The elevator has two large holes 2" by 4" cut into the back of the hoistway. The hoistway shall be repaired to be enclosed at its full length per the Missouri Minimum Standard. | 10/1/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | The elevator has two large holes 2" by 4" cut into the back of the hoistway. The hoistway shall be repaired to be enclosed at its full length per the Missouri Minimum Standard. | 9/2/2026 |