Inspection
Inspection Details
Equipment ID
9380
9380
Inspection Date
9/22/2020
9/22/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Nick Huzar
Nick Huzar
Relief Valve Pressure
350
350
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
ff32aca7-8b52-4b38-882b-26caccf6784f
ff32aca7-8b52-4b38-882b-26caccf6784f
Location
West County Center
80 W COUNTY CTR, SAINT LOUIS, MO
Phone: (314) 288-2020
80 W COUNTY CTR, SAINT LOUIS, MO
Phone: (314) 288-2020
Owner
Attn: Mike Baker
CBL Properties/West County center
80 West County Center, Des Peres, MO 63131
Phone: (314) 288-2034
Email: andrew.goldacker@cblproperties.com
CBL Properties/West County center
80 West County Center, Des Peres, MO 63131
Phone: (314) 288-2034
Email: andrew.goldacker@cblproperties.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Post Mo Stae certificate in machine room | 10/22/2019 | ||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 10/22/2019 | ||
A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | Machine room needs to be locked at all times. | 10/22/2019 | ||
A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | Top level door is missing two door gibs. | 10/22/2019 | ||
A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 210.1e | Gate switch exceeds minimum measurement for center opening doors. Reinspect. | 10/22/2019 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | There needs to be a working lit in the pit. | 10/22/2019 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency light not working. | 11/20/2019 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency alarm bell not working. | 11/20/2019 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 10/22/2019 | ||
A17.1-1996 : Elevators | 1.7 - Car door or gate | 1001.2(a)(7) | x | Adjust car door to cab clearance to 3/8 max - currently in excess of 1/2 inch. | 9/28/2020 | |
A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | Replace missing door gibbs on 5th floor and missing fire tab on 3rd floor. | 9/28/2020 | ||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Annual tag shows expired. | 11/30/2022 | ||
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Alarm bell does not work on 110v emergency power or normal power | 4/9/2024 | |
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Emergency light in the cab does not work | 4/9/2024 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Provide existing pit light to work. | |||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Provide current year tested fire extinguisher in the elevator machine room. | |||
A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 204.7 | Provide car top light to work. | |||
A17.1-1996 : Elevators | 3.8 - Top emergency exit | 204.1e | Provide means to secure car top exit. | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | Provide,on Phase II operations, call cancel feature to work. |