Inspection
Inspection Details
Equipment ID
7642
7642
Inspection Date
7/20/2017
7/20/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sheila Swett
Sheila Swett
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
Location
Mallincrodt Institute of Radiology
510 S Kingshighway Blvd, Ste 7, St. Louis, MO
Phone: (314) 707-0740
510 S Kingshighway Blvd, Ste 7, St. Louis, MO
Phone: (314) 707-0740
Owner
Mallinckrodt Institute of Radiology
510 S Kingshighway Blvd, St. Louis, MO 63110
510 S Kingshighway Blvd, St. Louis, MO 63110
Billing
Attn: Washington University School of Medicine
660 S Euclid Ave, Campus Box 8080, , MO 63110
660 S Euclid Ave, Campus Box 8080, , MO 63110
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Observed car emergency light not working. | 9/6/2018 |
| conversion | conversion | n/a | No | No | Observed pit requires cleaning. | 9/6/2018 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Observed emergency light not working. | 9/6/2018 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Observed door restricting device not working. | 9/22/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell not working when 110V removed. | 9/22/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and alarm bell not working when 110V removed. | 6/28/2019 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency power is existing but was not tested. | 6/28/2019 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | :Emergency power is existing but was not tested. | 10/11/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(d) | No | No | Maintenance Control Program does not comply with code. Missing maintenance procedures. | 9/14/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency power is existing but was not tested. | 1/26/2021 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Emergency lighting in car not working. | 8/6/2023 |