Inspection
Inspection Details
Equipment ID
21822
21822
Inspection Date
10/5/2020
10/5/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wayne Ingram
Wayne Ingram
Mechanic Name
Bryan Henson
Bryan Henson
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
40711b94-b6c6-46f3-987f-dfac0360eff1
40711b94-b6c6-46f3-987f-dfac0360eff1
Location
Joplin High School
2104 INDIANA AVE, JOPLIN, MO
Phone: (417) 625-5200
2104 INDIANA AVE, JOPLIN, MO
Phone: (417) 625-5200
Owner
Joplin R-VIII School District
1717 E 15TH ST, JOPLIN, MO 64804-0907
1717 E 15TH ST, JOPLIN, MO 64804-0907
Billing
Attn: Joplin R-8 School District
1301 S PICHER AVE, JOPLIN, MO 64804-0458
1301 S PICHER AVE, JOPLIN, MO 64804-0458
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Nec cab lighting needs to be wired direct and in conduit | 12/18/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.4 Car top light and Outlet | No | No | car top light needs to be guarded | 12/18/2020 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.3.1.2(j) | No | No | Fire extinguisher out of date | 12/18/2020 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post updated certificate | 12/18/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | Motion controlled machine room light switch | 12/18/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | required mounthly testing | 12/1/2023 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Update certificate | 12/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | no door restrictor | 1/23/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | No | No | Numbering must be the same for all elevator equipment | 12/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No MCP onsite | 12/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | Yes | Provide operational car door restriction, violation has not been corrected | 1/31/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate | 1/3/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP onsite | 1/3/2024 |