Inspection
Inspection Details
Equipment ID
2808
2808
Inspection Date
10/12/2020
10/12/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
17
17
External ID
99842172-9aee-47b7-9532-e7149ea8f36e
99842172-9aee-47b7-9532-e7149ea8f36e
Location
SSM-St. Joseph Health Center
300 1ST CAPITOL DR, SAINT CHARLES, MO
Phone: (636) 947-5000
300 1ST CAPITOL DR, SAINT CHARLES, MO
Phone: (636) 947-5000
Owner
Attn: Plant Operations
SSM Health St. Joseph Hospital – St. Charles
300 1st Capitol Dr, St. Charles, MO 63301
Phone: (314) 989-6134
Email: Marie.Odonnell@ssmhealth.com
SSM Health St. Joseph Hospital – St. Charles
300 1st Capitol Dr, St. Charles, MO 63301
Phone: (314) 989-6134
Email: Marie.Odonnell@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. | 10/14/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Phase I fire service key switch bezel at main landing is unreadable, replace same | 10/14/2025 | ||
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | x | Overspeed governor rope is damaged, replace same. Re-check pull out / pull thru when rope is replaced. Red-tagged. Re-inspection required | 1/18/2025 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | x | x | Car safeties were damaged during testing, repair or replace and re-inspect with full load, at contract speed. Red-tagged, Re-inspection required | 1/18/2025 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)6 | x | x | Overspeed governor speed switch is set too close to jaw tripping speed. Adjust and re-inspect. Red-tagged, re-inspection required | 1/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone in car shall work. Re-inspection required | 1/18/2025 | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | There is no fireman's emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required | 10/14/2025 | ||
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | There is no fireman's emergency service phase I instruction adjacent to the keyed switch at the primary egress floor, as required | 10/14/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Phase I fire service key switch bezel at main landing is unreadable, needs to be replaced | 10/14/2025 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency phone in car shall work. Re-inspection required | 4/22/2025 | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. | 10/14/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | x | Counterweight runby is 1 inch. Minimum runby is 6 inches. Hoist ropes need to be shortened to achieve at least 6 inches runby, needs repaired. Re-inspection required | ||
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | There is no fireman’s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. |