Inspection
Inspection Details
Equipment ID
9132
9132
Inspection Date
10/6/2020
10/6/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
fa5eab93-037c-4d3f-bf3b-7f33d73522c2
fa5eab93-037c-4d3f-bf3b-7f33d73522c2
Location
St. Louis University High School
4970 OAKLAND AVE, SAINT LOUIS, MO
Phone: (314) 531-0330
4970 OAKLAND AVE, SAINT LOUIS, MO
Phone: (314) 531-0330
Owner
St. Louis University High School
4970 OAKLAND AVE, SAINT LOUIS, MO 63110-1402
4970 OAKLAND AVE, SAINT LOUIS, MO 63110-1402
Billing
Attn: St. Louis University High School
4970 OAKLAND AVE, SAINT LOUIS, MO 63110-1402
4970 OAKLAND AVE, SAINT LOUIS, MO 63110-1402
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency lighting shall be operational. | 10/6/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency alarm shall be operational. | 10/6/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 5/28/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | 3.26.10 - The auxiliary power lowering operation shall be functional. | 6/2/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | 3.26.10 - The auxiliary power lowering operation shall be functional. (2nd Notice) | 5/27/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/28/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. (2nd Notice) | 5/28/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | CAR DOOR RESTRICTORS SHALL WORK AT ALL POINTS IN THE HOISTWAY WHEN THE CAR IS MORE THAN 18" ABOVE OR BELOW LANDING SILL. (front and rear) Multiple brackets are missing | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Battery Lowering shall be tested and operation verified. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current State Operating Permit shall be obtained and displayed in the Equipment Room. | 6/4/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Non-elevator related items shall not be stored in Machine Room. Remove mobile kiosk's. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Fire Service must be tested and properly documented monthly on Log Sheet located in the MCP. No logs present in Machine Room |