Inspection
Inspection Details
Equipment ID
12114
12114
Inspection Date
9/30/2020
9/30/2020
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
John Palmer, Jr
John Palmer, Jr
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
13
13
External ID
89541e8c-c735-4c2f-823b-5827344e0848
89541e8c-c735-4c2f-823b-5827344e0848
Location
MODOT- District Office
1590 Woodlake Dr, Chesterfield, MO
Phone: (314) 275-1509
Email: allen.lane@modot.mo.gov
1590 Woodlake Dr, Chesterfield, MO
Phone: (314) 275-1509
Email: allen.lane@modot.mo.gov
Owner
Attn: INTERAGENCY
MODOT-DISTRICT OFFICE/INTERAGENCY
1590 Woodlake Dr, Chesterfield, MO 63017
Phone: (314) 453-1709
Email: allen.lane@modot.mo.gov
MODOT-DISTRICT OFFICE/INTERAGENCY
1590 Woodlake Dr, Chesterfield, MO 63017
Phone: (314) 453-1709
Email: allen.lane@modot.mo.gov
Billing
Attn: INTERAGENCY
MODOT-DISTRICT OFFICE/INTERAGENCY
1590 Woodlake Dr, Chesterfield, MO 63017
Phone: (314) 453-1709
MODOT-DISTRICT OFFICE/INTERAGENCY
1590 Woodlake Dr, Chesterfield, MO 63017
Phone: (314) 453-1709
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 12/6/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | The in car stop switch shall be inoperable while in flight, while on Phase 1 return. | 1/30/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | NFPA70 620.91 - Machine room disconnecting means shall be provided with a compliant mechanical auxiliary contact to disconnect the load from the auxiliary power supply operation. | 1/30/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | Machinery, controllers, tanks, disconnects shall be properly numbered conspicuously. | 3/4/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | MCP fire service testing must be properly documented monthly on log sheet. | 3/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Permanently mounted pressure gauge shall be replaced with a calibrated gauge, having a calibration sticker that shows that it has been calibrated within the last year or install fitting for use of a detachable & calibrated portable gauge. | 3/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher is expired. | 3/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Adjust up-thrust roller bearings for proper clearance to door hanger track. (Multiple floors) | 3/4/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher is expired. | 2/29/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | MCP fire service testing must be properly documented monthly on log sheet. | 2/29/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | The overspeed valve shall be tested with the rated load on or before the next annual test. | 10/30/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The auxiliary power lowering shall be tested and function properly. | 10/16/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The OSV test on this unit was not performed and is due. This was not completed due to failure of the other unit at the facility. All other tests required for the inspection have been completed. The OSV shall be tested with a full load. | 10/16/2025 |