Inspection
Inspection Details
Equipment ID
10524
10524
Inspection Date
10/1/2020
10/1/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
John Ryan
John Ryan
Relief Valve Pressure
390
390
Slide
Governor Rope Pull
Door Closing Force
23/21
23/21
External ID
97fb3228-d07a-407c-910c-921920e12e55
97fb3228-d07a-407c-910c-921920e12e55
Location
Badenfest
8220 N BROADWAY, SAINT LOUIS, MO
Phone: (314) 231-5700
8220 N BROADWAY, SAINT LOUIS, MO
Phone: (314) 231-5700
Owner
Attn: Badenfest
The Habitat Company
8220 N Broadway, St. Louis, MO 63147
Phone: (314) 231-5700
Email: areeves@habitat.com
The Habitat Company
8220 N Broadway, St. Louis, MO 63147
Phone: (314) 231-5700
Email: areeves@habitat.com
Billing
Attn: Andy Reeves
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (618) 978-3338
Email: areeves@habitat.com
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (618) 978-3338
Email: areeves@habitat.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | The hoistway door tension on the bottom landing shall be adjusted to self-close. | 2/7/2020 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 2/7/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | The rear car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 2/11/2020 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Upon investigation, it was determined that the proper code should be ASME A17.1 1996 . Provide a proper plate on the front of the controller or mainline disconnect. | 2/7/2020 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | The machine room lighting was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | 2/7/2020 | ||
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | The hoistway door tension on the bottom landing shall be adjusted to self-close. | 7/21/2020 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 7/21/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Upon investigation, it was determined that the proper code should be ASME A17.1 1996. Provide a proper plate on the front of the controller or mainline disconnect. | 7/21/2020 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | The machine room lighting was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | 7/21/2020 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | 2 way communication is not working. Re-inspection required | 9/24/2024 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Two-way communication device is not working. Take corrective action and re-test. | 4/2/2025 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/21/2025 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No State opertating certificate in the machine room. | 11/21/2025 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit floor shall be cleaned. | 11/21/2025 |