Inspection
Inspection Details
Equipment ID
16590
16590
Inspection Date
9/28/2020
9/28/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Brent Davis
Brent Davis
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
ed972deb-cf99-42f7-8d0a-201f8fffd997
ed972deb-cf99-42f7-8d0a-201f8fffd997
Location
Parkway Apartments
4961 LACLEDE AVE, SAINT LOUIS, MO
Phone: (314) 361-1984
4961 LACLEDE AVE, SAINT LOUIS, MO
Phone: (314) 361-1984
Owner
Attn: Parkway Partnership
Parkway Partnership LLC
4961 LACLEDE AVE, SAINT LOUIS, MO 63108
Phone: (314) 361-1984
Email: karen@realcon.com
Parkway Partnership LLC
4961 LACLEDE AVE, SAINT LOUIS, MO 63108
Phone: (314) 361-1984
Email: karen@realcon.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lighting fixture has one bulb not operating, repair the fixture to provide adequate lighting in the machine room. | 7/10/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Written maintenance control program shall be provided on site. | 12/17/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide MCP | 2/16/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine room shall be cleaned of all items not required to maintain elevator | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work on emergency power or normal power. Repair or replace | 5/23/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit shall be cleaned of all dirt and debris | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean of dirt and debris. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Repair or replace basement hoistway door lock contact. It is damaged. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace missing car-top electrical box cover. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | All lamps shall work. Multiple lamps are not working. |