Inspection
Inspection Details
Equipment ID
1261
1261
Inspection Date
10/7/2020
10/7/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
526ea8cc-d0ba-471f-9354-b29cd9d92678
526ea8cc-d0ba-471f-9354-b29cd9d92678
Location
O'Fallon Senior Center
106 N MAIN ST, O FALLON, MO
Phone: (314) 574-1806
106 N MAIN ST, O FALLON, MO
Phone: (314) 574-1806
Owner
Attn: City of O'Fallon
City of O'Fallon
100 N MAIN ST, O FALLON, MO 63366
Phone: (000) 000-0000
City of O'Fallon
100 N MAIN ST, O FALLON, MO 63366
Phone: (000) 000-0000
Billing
Attn: City of O'Fallon
City of O'Fallon
100 N MAIN ST, O FALLON, MO 63366
Phone: (000) 000-0000
Email: mleonard@ofallon.mo.us
City of O'Fallon
100 N MAIN ST, O FALLON, MO 63366
Phone: (000) 000-0000
Email: mleonard@ofallon.mo.us
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post current State Certioficate in machine room | 9/14/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/14/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 10/7/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Provide a permanent, non-combustible pit sump pump cover. | 1/8/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 1/8/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 9/14/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/8/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 1/8/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 1/8/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | All machine room wiring shall be enclosed. Note: The machine room electrical receptacle is open with exposed wiring and shall be enclosed. | 1/8/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light shall be operational. | 1/8/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Part of the machine room walls are missing and shall be replaced with approved material. | 1/8/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lights shall be operational. | 1/8/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/8/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. (2nd Notice) | 1/8/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. (2nd Notice) | 1/8/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | All machine room wiring shall be enclosed. The machine room electrical receptacle is open with exposed wiring and shall be enclosed. (2nd Notice) | 1/8/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light shall be operational. (2nd Notice) | 1/8/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/8/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The phone shall establish 2-way communication. |