Inspection
Inspection Details
Equipment ID
7903
7903
Inspection Date
10/13/2020
10/13/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
200/420
200/420
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
b5180b85-ae96-4bf4-bd05-5863f14a03d1
b5180b85-ae96-4bf4-bd05-5863f14a03d1
Location
Siro OP Royal Oak, LLC
4960 LACLEDE AVE, SAINT LOUIS, MO
Phone: (000) 000-0000
4960 LACLEDE AVE, SAINT LOUIS, MO
Phone: (000) 000-0000
Owner
Attn: Royals Oak
Siro OP Royal Oak, LLC
4960 Laclede Ave, St. Louis, MO 63108
Phone: (000) 000-0000
Email: Richard.Woolard@reachltc.com
Siro OP Royal Oak, LLC
4960 Laclede Ave, St. Louis, MO 63108
Phone: (000) 000-0000
Email: Richard.Woolard@reachltc.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Fire caulk hole in the machine room wall. | 5/12/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Fire caulk hole in the pit wall. | 5/13/2023 | ||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Provide an emergency phone in the cab. | 7/3/2019 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | Properly secure the car top exit. | 5/12/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Make the car top run button operational. | 5/12/2023 | ||
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | Secure the smoke detector at top of hoistway. | 7/3/2019 | |
MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Properly guard the pit light. | 5/12/2023 | ||
A17.1-1996 : Elevators | 2.4 - Machine space | 1001.2(b)(4) | Fire caulk hole in machine room wall. (Repeat violation) | 5/12/2023 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Fire caulk hole in pit wall. (Repeat Violation) | 5/12/2023 | ||
A17.1-1996 : Elevators | 3.8 - Top emergency exit | 1001.2(c)(12) | Properly secure car top exit. (Repeat Violation) | 5/12/2023 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | An in car emergency phone shall be provided. (Repeat Violation) | 10/13/2020 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Properly guard the pit light. (Repeat Violation) | 5/12/2023 | ||
A17.1-1996 : Elevators | 1.7 - Car door or gate | 1001.2(a)(7) | Replace missing hoistway door sight guard at 4th floor. | 5/12/2023 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | The machine room shall be kept clean and all non-elevator related materials shall be removed from the machine room. | 5/12/2023 | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | The pit shall be kept clean. Clean the pit. | 5/12/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | The emergency lighting shall be operational. | 11/18/2021 | |
A17.1-1996 : Elevators | 2.4 - Machine space | 1001.2(b)(4) | Fire caulk hole in machine room wall. | 5/12/2023 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Fire caulk hole in pit wall. | 5/12/2023 | ||
A17.1-1996 : Elevators | 3.8 - Top emergency exit | 1001.2(c)(12) | Properly secure car top exit. | 5/12/2023 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | An in car emergency phone shall be provided. | 11/18/2021 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Properly guard the pit light. | 5/12/2023 | ||
A17.1-1996 : Elevators | 1.7 - Car door or gate | 1001.2(a)(7) | Replace missing hoistway door sight guard at 4th floor. | 5/12/2023 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 5/12/2023 | ||
A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 5/12/2023 |