Inspection
Inspection Details
Equipment ID
18403
18403
Inspection Date
10/5/2020
10/5/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Ronnie Morris
Ronnie Morris
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
36046cdc-b678-4864-a052-66ededc5f043
36046cdc-b678-4864-a052-66ededc5f043
Location
Express Scripts
1 EXPRESS WAY, SAINT LOUIS, MO
Phone: (314) 996-0900
1 EXPRESS WAY, SAINT LOUIS, MO
Phone: (314) 996-0900
Owner
Express Scripts
1 EXPRESS WAY, SAINT LOUIS, MO 63121-1824
1 EXPRESS WAY, SAINT LOUIS, MO 63121-1824
Billing
Attn: Express Scripts Inc
8455 UNIVERSITY PLACE DR # 2, SAINT LOUIS, MO 63121-1825
8455 UNIVERSITY PLACE DR # 2, SAINT LOUIS, MO 63121-1825
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | No | No | Auxiliary power lowering device shall be operational. | 10/5/2020 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 6/1/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it. Note: The MO state certificate is not posted in the machine room as required. | 6/22/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. Note: The person answering the phone cannot hear the person making the call from the elevator. | 6/15/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no State Operating Certificate in the machine room. | 8/14/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | The oil log and fire service log are not being updated monthly. | 8/14/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace faded in-car capacity plate. | 8/14/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace faded in-car phase 2 instruction plate. | 8/14/2026 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Battery lowering shall be operational. | 8/14/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/14/2026 |