Inspection
Inspection Details
Equipment ID
13227
13227
Inspection Date
10/18/2020
10/18/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Relief Valve Pressure
n/a
n/a
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
e4218d4c-70c5-474d-84cd-b2dd2035e604
e4218d4c-70c5-474d-84cd-b2dd2035e604
Location
Con Agra Frozen Foods
200 N BANQUET DR, MARSHALL, MO
Phone: (660) 236-6107
200 N BANQUET DR, MARSHALL, MO
Phone: (660) 236-6107
Owner
Attn: Con Agra Frozen Foods
Con Agra Frozen Foods
200 N BANQUET DR, MARSHALL, MO 65340
Phone: (660) 236-6065
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
Con Agra Frozen Foods
200 N BANQUET DR, MARSHALL, MO 65340
Phone: (660) 236-6065
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | FS No Audible or Visual Signals on Phase I recall. | 10/12/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Phase II operation not working. | 10/12/2018 |
| A17.1-1996 : Elevators | 4.4 - Hoistway door locking devices | 111 | Yes | Yes | Freight Bi-Parting Landing Door Mechanical lock broken doors could be opened by separating with car away from landing. | 10/17/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone not working | 10/18/2020 |
| A17.1-1996 : Elevators | 4.1 - Car platform guard | 203.9 | No | No | toe guard needs to be replaced only covers less than half of opening | 1/1/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | lot of debris in pit 106.2a | 1/1/2023 |
| A17.1-1996 : Elevators | 4.1 - Car platform guard | 203.9 | No | No | needs new platform guard installed | 1/1/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working | 1/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working | 5/24/2022 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Overspeed valve tripping above 140% of down speed. Rusted up so can't adjust | 1/1/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working | 11/16/2022 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | In case of fire don't use elevator signage needed | 1/1/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Phase 2 key switch not working | 11/16/2022 |
| A17.1-2016 : Elevators | 1.2 - Stop Switches | 8.11.2.1.1(b) | No | No | In car stop switch works in up direction but not down. May tie in to phase 2 key switch problem. Used as no rider so left running | 1/23/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Telephone Incoming Line is bad must replace or repair & retest. | 1/6/2023 |