Inspection
Inspection Details
Equipment ID
20885
20885
Inspection Date
10/9/2020
10/9/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
13
13
External ID
5844e767-ff6f-469e-8076-68567d8552db
5844e767-ff6f-469e-8076-68567d8552db
Location
Express Scripts
8640 EVANS AVE, SAINT LOUIS, MO
Phone: (314) 496-6032
8640 EVANS AVE, SAINT LOUIS, MO
Phone: (314) 496-6032
Owner
Express Scripts
8640 EVANS AVE, SAINT LOUIS, MO 63134-2903
8640 EVANS AVE, SAINT LOUIS, MO 63134-2903
Billing
Attn: Express Scripts
8640 EVANS AVE, SAINT LOUIS, MO 63134-2903
8640 EVANS AVE, SAINT LOUIS, MO 63134-2903
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/8/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | No | No | Subsequent to the first stop of the car following the opening of the tail switch tension switch, the car shall remain inoperative until the switch is manually reset. | 9/8/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 9/12/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Replace the missing guides on the counterweight. | 9/8/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 9/8/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Fire gibs shall be installed. | 11/3/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 11/3/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | Door close button behind locked fire panel shall work. | 11/3/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Fire gibs shall be installed. | 11/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | Door close button behind locked fire panel shall work. | 11/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/12/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | MCP, including PM records and monthly fire service test log, not being properly documented. | 12/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing counterweight guide inserts. | 12/12/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 12/16/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch. | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. Re-inspection required | 4/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | No | No | Provide testing of the elevator emergency power selector switch. | 4/7/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | During the emergency power test, the elevator did run on emergency power, but the emergency power jewel did not illuminate at the main lobby, repair jewel. Re-inspection required | 8/13/2026 |