Inspection
Inspection Details
Equipment ID
22069
22069
Inspection Date
10/9/2020
10/9/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
eed8458e-d0f2-43c0-89dd-3971957d0131
eed8458e-d0f2-43c0-89dd-3971957d0131
Location
Express Scripts-HVF
4600 N HANLEY RD, BERKELEY, MO
Phone: (314) 522-5743
4600 N HANLEY RD, BERKELEY, MO
Phone: (314) 522-5743
Owner
Attn: Express Scripts - HVF
Express Scripts - HVF
4600 N HANLEY RD, BERKELEY, MO 63134
Phone: (000) 000-0000
Email: ESI-Invoices@Dataserv-stl.com
Express Scripts - HVF
4600 N HANLEY RD, BERKELEY, MO 63134
Phone: (000) 000-0000
Email: ESI-Invoices@Dataserv-stl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 2.14.7 | No | No | 2.7.9.1 - The light in the hoistway shall be operational. | 2/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Fire tabs are missing from the hoistway doors. The hoistway door safety retainers shall all be installed properly. | 12/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | The MCP needs to be up to date. A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 2/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 12/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. Note: This violation has been cited in 2021, 2022, and now 2023. Testing shall be witnessed within 30 days or operating certificate may be revoked and elevators locked out of service. | 1/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 2/15/2024 |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.7.2 Seizing of Rope Ends | No | No | 2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. | 2/15/2024 |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.5 Wedge Rope Sockets | No | No | 2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced. | 2/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communications/phone in car not working. | 8/14/2025 |