Inspection
Inspection Details
Equipment ID
21256
21256
Inspection Date
10/5/2020
10/5/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Zachary Thieme
Zachary Thieme
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
9e0116c2-f105-4c3c-b05e-026c18496164
9e0116c2-f105-4c3c-b05e-026c18496164
Location
MO Baptist Hospital-West Pavilion
3015 N NEW BALLAS, ST. LOUIS, MO
Phone: (314) 996-5412
3015 N NEW BALLAS, ST. LOUIS, MO
Phone: (314) 996-5412
Owner
Attn: MO Baptist Medical
MO Baptist Medical Center
3015 N BALLAS RD, SAINT LOUIS, MO 63131
Phone: (314) 996-5412
Email: gerald.erickson@bjc.org
MO Baptist Medical Center
3015 N BALLAS RD, SAINT LOUIS, MO 63131
Phone: (314) 996-5412
Email: gerald.erickson@bjc.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.11.2.1.3(w) | No | No | First floor interlock cover is missing and shall be replaced. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.2.3 | Yes | No | Governor will not electrically set or reset. Governor shall be repaired and tested. | 5/29/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Emergency fire service shall be tested. | 5/29/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | Clean the car top. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | No | No | Provide numbering on car top. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Clean the pit. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | 2.4.3 - Provide counterweight runby sign in the pit. | 7/31/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.11.2.1.3(w) | No | No | Provide missing hoistway door interlock cover at 1st floor. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.40 - Maintenance Records | 2.26.1.4 Inspection Operation | No | No | Provide MCP. | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Governor will not electrically set or reset. Governor shall be repaired and tested. (Violation not cleared from previous annual inspection) | 11/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Automatic return to the fire recall floor after coming off Phase 2 fire service does not work and shall be repaired. Violation corrected on 9/21/2020 and scheduled for re-inspection on 10/5/2020. | 10/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/16/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | Yes | No | Car went down during the inspection. Two cables slipped out of the under sling. | 5/28/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | The elevator went down during the annual inspection and category 5 test. The following testing items still need to be completed: 1. Door pressure., 2. Inspection of top of car., 3. Inspection of pit., 4. Fire service., 5. Emergency power test., 6. Complete entire category 5 test. | 5/28/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power and fire service need to be tested. | 10/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light does not work. | 10/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit is dirty. Clean the pit. | 10/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | In 2023 this elevator inspection was stopped due to a mechanical failure. Almost all of the annual inspection and the complete category 5 test still needed to be completed. The annual was completed 5/28/24 except for fire service and emergency power testing but the category 5 test has not been completed to date. A category 5 test need to be performed and witnessed in its entirety. | 10/21/2025 |