Inspection
Inspection Details
Equipment ID
12525
12525
Inspection Date
9/28/2020
9/28/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Andrew Schmitz
Andrew Schmitz
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
f2c50fca-6183-4d5d-8c18-bb53e943a04d
f2c50fca-6183-4d5d-8c18-bb53e943a04d
Location
Forest Park Community College
5600 OAKLAND AVE, SAINT LOUIS, MO
Phone: (618) 978-5176
5600 OAKLAND AVE, SAINT LOUIS, MO
Phone: (618) 978-5176
Owner
Attn: St. Louis CC
St. Louis Community College
300 S BROADWAY, SAINT LOUIS, MO 63102
Phone: (314) 435-9505
Email: JDuarte@stlcc.edu
St. Louis Community College
300 S BROADWAY, SAINT LOUIS, MO 63102
Phone: (314) 435-9505
Email: JDuarte@stlcc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | The car top run station shall be made operational. | 12/20/2019 |
| conversion | conversion | n/a | No | No | The top of car light shall be made operational. | 2/20/2020 |
| conversion | conversion | n/a | No | No | Fire extinguisher is expired. | 2/20/2020 |
| conversion | conversion | n/a | No | No | Cab lights shall be operational. | 2/20/2020 |
| conversion | conversion | n/a | No | No | The pit light shall be operational. | 2/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | The in car lighting shall be operational. | 2/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | The pit lighting shall be operational. | 2/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.3 - Top-of-car operating device | 8.11.2.1.3(c) | No | No | The car top inspection station is not operational and shall be repaired. | 2/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | The pit light shall be operational. | 2/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The cab lights and emergency cab lighting shall be operational. | 9/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.3 - Top-of-car operating device | 8.11.2.1.3(c) | No | No | Top of car run station shall be operational. | 2/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.3.1.2(c) | No | No | The machine room lighting shall be operational. | 2/20/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The emergency lighting shall be operational when the 110v source is removed. | 2/3/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | A set of wiring diagrams shall be provided in the elevator machine room. | 3/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 4/22/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Wiring diagrams are missing. | 4/22/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 8.11.2.1.3(b) | No | No | The car top light shall be operational. | 4/22/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | The fire extinguisher is expired. | 6/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Need a set of prints/wiring diagrams in the machine room. | 2/9/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 2.12.6 | Yes | No | Need to repair or replace pull string box on the bottom floor. | 4/22/2025 |