Inspection
Inspection Details
Equipment ID
12453
12453
Inspection Date
10/22/2020
10/22/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Brent Bonham
Brent Bonham
Relief Valve Pressure
530
530
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
65da171e-5bb0-4c65-bc73-91b91445e6a8
65da171e-5bb0-4c65-bc73-91b91445e6a8
Location
Mosaic Life Care
5325 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 271-6000
5325 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 271-6000
Owner
Attn: St. Joseph Downtown Development LLC
St. Joseph Downtown Development LLC
5325 FARAON ST, SAINT JOSEPH, MO 64506
Phone: (816) 271-7539
Email: James.richards@mymlc.com
St. Joseph Downtown Development LLC
5325 FARAON ST, SAINT JOSEPH, MO 64506
Phone: (816) 271-7539
Email: James.richards@mymlc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(c) | No | No | Test and log firefighter operation monthly | 11/17/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(b)(4) | No | No | Post emergency evacuation of passengers procedure inside machine | 11/17/2020 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Room and Machinery Space | No | No | Remove non-elevator related material from elevator machine room | 11/17/2020 |
| A17.1-2016 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 | No | No | Cylinder drain line shall drain into pit collection container of no more than 5 gallon container. Remove scavenger pump from pit. | 11/17/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside machine room | 11/17/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | Install FEO-K1 keyswitches. All elevators in the same building shall have firefighter keyswitches operable by the same key. | 10/28/2022 |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.6.4.19.8 | Yes | No | Door pressure exceeds 30# | 10/28/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test operation of elevator on emergency power with an inspector present | 10/28/2022 |
| A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.1 Examination and Maintenance | No | No | Replace plunger seal. Seal leaks excessively | 2/1/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | MRL not up to date | 2/1/2024 |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.6.4.19.8 | Yes | No | Door force exceeds 30 pounds | 10/25/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 1/5/2024 |