Inspection
Inspection Details
Equipment ID
20536
20536
Inspection Date
5/22/2018
5/22/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Joel Vorbeck
Joel Vorbeck
Relief Valve Pressure
Slide
Governor Rope Pull
na
na
Door Closing Force
23
23
External ID
9068b8ab-f4b8-4db9-b538-120e59f2db40
9068b8ab-f4b8-4db9-b538-120e59f2db40
Location
UMKC Cherry Hall
5030 CHERRY ST, KANSAS CITY, MO
5030 CHERRY ST, KANSAS CITY, MO
Owner
UMKC- Parking Structure
1011 E 51ST ST, KANSAS CITY, MO 64110-2201
1011 E 51ST ST, KANSAS CITY, MO 64110-2201
Billing
Attn: UMKC- Campus Facilities
1011 E 51ST ST, KANSAS CITY, MO 64110-2201
1011 E 51ST ST, KANSAS CITY, MO 64110-2201
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | post current copy of state operating certificate in the machine room | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | post monthly fire service test log in the machine room | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | provide complete MCP in the machine room addording to code | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.2 - Car top light and outlet | 8.11.2.1.3(b) | replace car top light bulb, it was burnt out | |||
A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | the copy of the state operating certificate posted in the machine room is to be updated annually | |||
A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.2.1.5(a) | replace pit light bulb, it is burnt out | |||
A17.1-2016 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | bottom landing hoistway access keyswitch is not working | |||
A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(j) | Machine room fire extinguisher inspection tag is from 2019, it is to be inspected and tagged annually. | |||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2019 | |||
A17.1-2016 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(i) | the controller room air conditioner does not appear to be working, repair the air conditioner so the room is maintained at the recommended temperature per the manufacturer's data tag (2.7.9.2) | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | machine room air conditioner is not working, repair air conditioner so machine room is maintained at the manufacturer's recommended temperature range and humidity | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | Machine room air conditioner is not working, repair air conditioner so room is maintained at the manufacturer's recommended temperature range | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.7 - Car door or gate | 2.14.4 | x | Repair bent pick up roller assembly on landing one hoistway door (2.14.4.2.4) | 8/30/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | Emergency light battery is dead and needs to be replaced | 8/30/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | Repair AC unit and maintain manufacturer's recommended operating range |