Inspection
Inspection Details
Equipment ID
17310
17310
Inspection Date
10/5/2020
10/5/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Angelo Consiglio
Angelo Consiglio
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
98dea563-c1d5-4cc4-81f2-d248b45423f4
98dea563-c1d5-4cc4-81f2-d248b45423f4
Location
Harrahs Casino
784 CASINO CENTER DR, MARYLAND HEIGHTS, MO
Phone: (314) 770-8278
784 CASINO CENTER DR, MARYLAND HEIGHTS, MO
Phone: (314) 770-8278
Owner
Attn: John Koshinski
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO 63043
Phone: (314) 770-8278
Email: John.Koshinski@pngaming.com
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO 63043
Phone: (314) 770-8278
Email: John.Koshinski@pngaming.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Weight rods loose on counter weights | 7/30/2019 |
| conversion | conversion | n/a | No | No | Replace missing counterweight roller | 7/30/2019 |
| conversion | conversion | n/a | No | No | Alarm bell does not work | 7/30/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Car runs with car door open 4" maximum is 2" | 8/6/2018 |
| conversion | conversion | n/a | No | No | Car door restrictor does not work. | 7/30/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Cab emergency lights do not work | 8/6/2018 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | Yes | No | Weight rods on counterweight are loose. | 7/30/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 10/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Outer insulating jacket is coming off of traveling cable under car, no conductors exposed. Repair or replace | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Traveling cable is damaged in several spots and needs to be replaced. Re-inspection required | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room |