Inspection
Inspection Details
Equipment ID
2725
2725
Inspection Date
5/29/2018
5/29/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Joseph Blankenship
Joseph Blankenship
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
16
16
External ID
fc9e65d1-d062-4f42-a7a4-318377ebb45c
fc9e65d1-d062-4f42-a7a4-318377ebb45c
Location
Student Success Center #2
5000 HOLMES ST, KANSAS CITY, MO
5000 HOLMES ST, KANSAS CITY, MO
Owner
UMKC- Parking Structure
1011 E 51ST ST, KANSAS CITY, MO 64110-2201
1011 E 51ST ST, KANSAS CITY, MO 64110-2201
Billing
Attn: UMKC- Campus Facilities
1011 E 51ST ST, KANSAS CITY, MO 64110-2201
1011 E 51ST ST, KANSAS CITY, MO 64110-2201
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | perform monthly fire service test and post log in the machine room | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | post current copy of state certificate in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | provide complete MCP in the machine room according to 8.6.1.4 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | machine room fire extinguisher inspection tag expired | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | the machine room fire extinguisher was last tagged in 2015, have the fire extinguisher inspected and tagged annually | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | the monthly test log for fire fighter's service has not been filled out since January | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2019 | |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | fire service key is not the same as the elevator in the center of the building, the elevator in the center of the building uses FEO-K1 key the bookstore elevator needs to use the same key | |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | Fire service key is not the same as the elevator in the center of the building, the elevator in the center of the building uses a FEO-K1 key, upgrade the keyswitch so it is the same as the other elevator in the building | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Label the hoistway side of landing doors with the floor identification number in 4 inch letters |