Equipment ID
22271
22271
Inspection Date
10/12/2020
10/12/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
550
550
Slide
Governor Rope Pull
Door Closing Force
14
14
External ID
80766010-81d3-4e1a-9323-961d1cf5a978
80766010-81d3-4e1a-9323-961d1cf5a978
Location
Residences @ New Longview Apt
3301 SW KESSLER DR, LEES SUMMIT, MO
Phone: (913) 422-5555
3301 SW KESSLER DR, LEES SUMMIT, MO
Phone: (913) 422-5555
Owner
Attn: NorthPoint Development
NorthPoint Development
5015 NW CANAL ST STE 200, RIVERSIDE, MO 64150
Phone: (000) 000-0000
NorthPoint Development
5015 NW CANAL ST STE 200, RIVERSIDE, MO 64150
Phone: (000) 000-0000
Billing
Attn: Residences @ New Longview Apt.
NorthPoint Development
3301 SW KESSLER DR, LEES SUMMIT, MO 64081
Phone: (000) 000-0000
Email: amiddaugh@jvmrealty.com
NorthPoint Development
3301 SW KESSLER DR, LEES SUMMIT, MO 64081
Phone: (000) 000-0000
Email: amiddaugh@jvmrealty.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | do not store non-elevator relaed equipment in the machine room | 8/17/2018 |
| conversion | conversion | n/a | No | No | repair door restrictor | 8/17/2018 |
| A17.2-2014 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1.18.1(a) | No | No | car door restrictor missing parts and needs repaired | 4/30/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Perform monthly fire service test and post log in the machine room. | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | No | No | remove large peice of PVC pipe laying on the pit floor that is not hooked to anything | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | 2.2.2.6 sumps in pits shall be covered, it is leaning against the wall without the needed cutouts to be installed over the sump hole | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | Repair the door restrictor, it is missing parts | 10/12/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not work, the phone line has dial tone but it would not dial out | 10/12/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | need to fill out the monthly fire service test log in the machine room every month | 1/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | post cop of the state operating certificate in the machine room | 1/1/2021 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the machine room is from 2017, a new copy is to be displayed every year | 12/1/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | No | No | The firefighters service test log is not being filled out monthly. | 12/1/2022 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.11.3.1.2(h) | No | No | non elevator related material is not to be stored in the elevator machine room | 12/1/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.3.1.5(a) | No | No | water in the oil collection pan | 12/1/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.3.1.5(a) | No | No | the sump pump is plugged in the GFCI outlet, it should be plugged into the single outlet that was provided for the sump pump | 12/1/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.3 | No | No | water in pit, hydraulic line completely submerged in water, sump pump is not even plugged in, permanent provisions shall be made to prevent accumulation of ground water in the pit | 7/10/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Water and pit, hydraulic line completely submerged in water, sump pump is not even plugged in, maintain dry pit. Repeat from 2022 (2.2.2.3) | 6/25/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Do not store non-elevator related items in the machine room (8.6.4.8.2) | 6/25/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone was not answered | 11/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Do not store non-elevator related items in the machine room | 12/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post a current copy of the state operating certificate in the Elevator machine room. The one that’s on display is several years old. | 12/15/2024 |