Inspection
Inspection Details
Equipment ID
9921
9921
Inspection Date
10/14/2020
10/14/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Richard Rickermann
Richard Rickermann
Relief Valve Pressure
540
540
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
1c03b88e-b2b8-4b4c-a5c0-25676ebbb157
1c03b88e-b2b8-4b4c-a5c0-25676ebbb157
Location
Doctor's Medical Office Bldg
3660 VISTA AVE, SAINT LOUIS, MO
Phone: (314) 977-2966
3660 VISTA AVE, SAINT LOUIS, MO
Phone: (314) 977-2966
Owner
Attn: Barth Breneman
St. Louis University
3545 LINDELL BLVD 2nd Floor, SAINT LOUIS, MO 63103
Phone: (314) 977-2966
Email: barth.breneman@slu.edu
St. Louis University
3545 LINDELL BLVD 2nd Floor, SAINT LOUIS, MO 63103
Phone: (314) 977-2966
Email: barth.breneman@slu.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light does not work. | 2/26/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(a) Elevators Placed in Inactive Status | Yes | Yes | Elevator placed in Inactive status | 5/4/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. Rr-inspection required | 9/20/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The door operator motor would not operate on the day of inspection. Without the door operator being operational, door pressure and Fireman’s Emergency Service operation could not be tested. | 10/26/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair this phone for proper operation and passenger safety. Reinspection required. | 10/26/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time due to the door operator is not in operation.Fireman’s Service operation and door pressure tested before the inspection is completed. | 10/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 11/25/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The door operator motor would not operate on the day of inspection. Without the door operator being operational, door pressure and Fireman’s Emergency Service operation could not be tested. | 12/27/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair this phone for proper operation and passenger safety. Reinspection required. | 12/27/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time due to the door operator is not in operation.Fireman’s Service operation and door pressure tested before the inspection is completed. | 12/27/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 11/25/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair this phone for proper operation and passenger safety (the building is not currently occupied) Reinspection required. | 11/25/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative emergency phone |