Inspection
Inspection Details
Equipment ID
5428
5428
Inspection Date
6/15/2018
6/15/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
1751a693-03f5-4461-8651-156ca7b62d8c
1751a693-03f5-4461-8651-156ca7b62d8c
Location
Springfield Christian Health Care
3535 E CHEROKEE ST, SPRINGFIELD, MO
3535 E CHEROKEE ST, SPRINGFIELD, MO
Owner
Springfield Christian Health Care
5305 W VILLAGE PKWY STE 12, ROGERS, AR 72758-8116
5305 W VILLAGE PKWY STE 12, ROGERS, AR 72758-8116
Billing
Attn: Springfield Christian Health Care East
3535 E CHEROKEE ST, SPRINGFIELD, MO 65809-2829
3535 E CHEROKEE ST, SPRINGFIELD, MO 65809-2829
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Telephone not working-no voltage on line to controller-reinspect required | 6/15/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | No | No | telephone not working--line voltage is low--second notice | 6/19/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post updated certificate | 1/11/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No maintenance records | 1/11/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Maintain mounthly log | 1/11/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post updated certificate | 1/11/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Cannot use cab lighting to power door safety edge: NEC 620.22 | 11/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Must Provide and Maintain all required MCP documentation and logs. 8.6.1.4.1 | 1/11/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Must perform and document Monthly Fire Service test. 8.6.10.1 | 1/11/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Must post current state operating Cert. in the Mach room. 5.100(2) | 1/11/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Car Lights and Fan must be a dedicated circuit. NEC 620.22 (Currently door safety edge is wired with Cab Light and fan) | 1/11/2023 |