Inspection
Inspection Details
Equipment ID
14533
14533
Inspection Date
6/15/2018
6/15/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gerald Glynn
Gerald Glynn
Mechanic Name
Relief Valve Pressure
610
610
Slide
Governor Rope Pull
Door Closing Force
FR 27 R 28
FR 27 R 28
External ID
f06fd0c0-0b85-43f1-b972-8e578930b7de
f06fd0c0-0b85-43f1-b972-8e578930b7de
Location
Hickory Hills Country Club
3909 E CHERRY ST, SPRINGFIELD, MO
3909 E CHERRY ST, SPRINGFIELD, MO
Owner
Hickory Hills Country Club
3909 E CHERRY ST, SPRINGFIELD, MO 65809-1509
3909 E CHERRY ST, SPRINGFIELD, MO 65809-1509
Billing
Attn: Hickory Hills Country Club
PO BOX 11046, SPRINGFIELD, MO 65808-1046
PO BOX 11046, SPRINGFIELD, MO 65808-1046
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Red Tag) | Yes | No | telephone does not work | 5/3/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 1.5 telephone will not call out but alarm still works | 4/9/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | needs current certificate posted in machine room | 4/9/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | H(4)/2.5/8.11.2.1.2(e). Non-elevator related items shall not be stored in Machine Room. | 5/1/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | 2021&2022 Violation: 11 CSR 40-5.100(2) : Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. Wrong unit on display (inactive dumbwaiter 2018) | 5/2/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | 2021&2022 Violation: H(4)/2.5/8.11.2.1.2(e). Non-elevator related items shall not be stored in Machine Room. (Pictures, ) | 5/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co.) | 5/1/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | H(2) / 101.3d(1)(b) Machine room door shall be self-closing and self-locking ( Door sticks and won't self-close fully) | 5/1/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate in machine room | 5/1/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator items from machine room | 5/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP in machine room | 5/1/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Provide current state operating certificate | 5/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP in machine room | 5/1/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator equipment from machine room | 5/1/2024 |