Inspection
Inspection Details
Equipment ID
16928
16928
Inspection Date
10/20/2020
10/20/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
15
15
External ID
f134f70c-6dd1-423e-9ee9-a8b61169ee2b
f134f70c-6dd1-423e-9ee9-a8b61169ee2b
Location
Abbey Senior Health
206 N MAIN STREET, O FALLON, MO
Phone: (636) 240-3420 Ext: 129
206 N MAIN STREET, O FALLON, MO
Phone: (636) 240-3420 Ext: 129
Owner
Attn: Staci Meyer
Abbey Senior Health
206 N MAIN ST, O FALLON, MO 63366
Phone: (636) 240-5754 Ext: 129
Email: smeyer@abbeyseniorhealth.com
Abbey Senior Health
206 N MAIN ST, O FALLON, MO 63366
Phone: (636) 240-5754 Ext: 129
Email: smeyer@abbeyseniorhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide code compliant maintenance control program documents. | 1/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.7.1.8 | No | No | Provide a code compliant code data tag. | 1/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.19 - Gears, bearings, and flexible couplings | 8.6.1.6.2 | No | No | Verify the oil level in the hoist machine. | 1/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.11.2.1.5(j) | Yes | Yes | The following items still need to be tested for completion of Category 5 Test: Set the car safeties, test ascending car over speed, and confirm proper operation of load weighing device. | 11/18/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.19 - Gears, bearings, and flexible couplings | 8.11.2.1.2(q) | No | No | Determine condition of hoist machine bearings and gears. Machine is making loud noise when running down with capacity load. | 1/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.18 - Traction drive machines | 8.11.2.1.2(p) | Yes | No | Controller is indicating 125% load when car is loaded at capacity. | 1/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be operational. | 2/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | Phase 2 fire service not operating properly. | 2/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in-car emergency lights shall be operational. | 4/3/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.7 Phase 2 Operation Panel (Re-Inspection) | Yes | No | The door open button in the firefighters phase two panel is intermittently sticking in the actuated position and shall be repaired or replaced. | 4/3/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/1/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Rope shall be shortened for proper runby. | 10/14/2025 |