Inspection
Inspection Details
Equipment ID
22195
22195
Inspection Date
10/22/2020
10/22/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Ross Colligan
Ross Colligan
Relief Valve Pressure
300
300
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
82094a5d-05b0-4742-b183-5b2b55af7a92
82094a5d-05b0-4742-b183-5b2b55af7a92
Location
Wilkinson EEC
1921 PRATHER AVE, SAINT LOUIS, MO
Phone: (314) 645-1202
1921 PRATHER AVE, SAINT LOUIS, MO
Phone: (314) 645-1202
Owner
Attn: UNK
St.Louis Board of Education
801 N 11TH ST, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Email: Rosmon.Johnson@slps.org
St.Louis Board of Education
801 N 11TH ST, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Email: Rosmon.Johnson@slps.org
Billing
Attn: Sandy Russell
Century Elevator
P.O. Box 510571, St. Louis, MO 63151
Phone: (314) 846-3500
Email: sandy@centuryelevatorservice.com
Century Elevator
P.O. Box 510571, St. Louis, MO 63151
Phone: (314) 846-3500
Email: sandy@centuryelevatorservice.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Remove all non-elevator related equipment from the machine room. | 10/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide an ABC type fire extinguisher in the machine room. | 10/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-locking. | 10/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.26.4 | No | No | Provide feeder location on main line disconnect. | 10/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.26.4 | No | No | Provide feeder location on 110V cab lighting disconnect. | 10/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Provide sign on machine room door stating "Authorized Personnel Only". | 10/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.11.2.1.2(e) (Re-Inspection) | No | No | Remove all non-elevator related items from the machine room. | 10/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | The fire extinguisher in the machine room is expired. | 10/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | Label machine room equipment door. | 10/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | The machine room shall not be used for the storage of non-elevator related materials. | 10/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 5/18/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lighting shall be operational. | 5/18/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | This elevator has an overspeed valve device installed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Overspeed valve shall be tested and a reinspection is required. | 11/5/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | 5 year annual testing has not been completed on the elevator at this time. The weight test shall be performed, overspeed valve tested, and full load pressure recorded before the inspection is completed. | 11/5/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Need to install flooring in elevator | 1/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 1/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | This elevator has an overspeed valve device installed and is now required to have a 5 year full load test performed. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Overspeed valve shall be tested and a reinspection is required. | 1/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | 5 year annual testing has not been completed on the elevator at this time. The weight test shall be performed, overspeed valve tested, and full load pressure recorded before the inspection is completed. | 1/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required. 2nd notice, a third notice will result in unit being Red-tagged and removed from service |