Inspection
Inspection Details
Equipment ID
2216
2216
Inspection Date
10/28/2020
10/28/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Brent Bonham
Brent Bonham
Relief Valve Pressure
Na
Na
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
75559d7e-3658-4429-9c03-814ab575cf10
75559d7e-3658-4429-9c03-814ab575cf10
Location
Mosaic Life Care
5325 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 271-6000
5325 FARAON ST, SAINT JOSEPH, MO
Phone: (816) 271-6000
Owner
Attn: St. Joseph Downtown Development LLC
St. Joseph Downtown Development LLC
5325 FARAON ST, SAINT JOSEPH, MO 64506
Phone: (816) 271-7539
Email: James.richards@mymlc.com
St. Joseph Downtown Development LLC
5325 FARAON ST, SAINT JOSEPH, MO 64506
Phone: (816) 271-7539
Email: James.richards@mymlc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Test and log firefighter operation monthly | 11/17/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post correct firefighter instructions inside elevator | 11/17/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside machine | 11/17/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post firefighter operating instructions next to hall fire keyswitch | 11/11/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Replace incorrect firefighter instructions on car operating panel | 11/11/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | Install FEO-K1 keyswitch. All elevators in the same building shall have firefighter keyswitches operable by the same key. | 11/11/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Momentary operation of door open button allows doors to fully open. 14 days to fix or red tagged | 11/10/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | 11/11/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test operation of elevator on emergency power with an inspector present | 11/10/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not operate | 12/8/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test operation of elevator on emergency power | 12/8/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator did not operate on standby emergency power when selected by the lobby standby selection switch | 10/26/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Identification markings on lobby panel standby selection switch for elevators 4 and 5 are illegible | 1/11/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace incorrect firefighter instructions on car operating panel | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency bell does not operate | 11/9/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test operation of elevator on emergency power | 11/9/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | MRL not up to date | 12/7/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency bell does not operate | 10/24/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test emergency power operation | 12/13/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 1/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace standby selection switch on lobby panel. Selection switch does not select a car to run on emergency power. Both of the duplexed elevators run simultaneously on emergency power. | 2/2/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency power was not tested. | 11/13/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Yes | No | Keyswitch bezels are illegible. | 11/13/2025 |