Inspection
Inspection Details
Equipment ID
11316
11316
Inspection Date
10/21/2020
10/21/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
fe42a841-0160-4439-b2fd-62d147f2ea5a
fe42a841-0160-4439-b2fd-62d147f2ea5a
Location
900 N Tucker Building, LLC
900 N Tucker Blvd, St. Louis, MO
Phone: (314) 340-8754
Email: mattc@900north.biz
900 N Tucker Blvd, St. Louis, MO
Phone: (314) 340-8754
Email: mattc@900north.biz
Owner
Attn: 900 N Tucker Building, LLC
900 N Tucker Building, LLC
900 N Tucker Blvd, St. Louis, MO 63101
Phone: (314) 340-8754
Email: mattc@900north.biz
900 N Tucker Building, LLC
900 N Tucker Blvd, St. Louis, MO 63101
Phone: (314) 340-8754
Email: mattc@900north.biz
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Program emergency phone to ring to a 24 hr monitoring station. | 11/6/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Close holes at top of hoistway. | 11/5/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | The fire tabs (Hoistway Door Safety Retainers) were not installed on the hoistway doors at the time of construction. The fire tabs shall be installed to retain the hoistway doors in the closed position if the primary means fails. | 6/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | No | No | The signage for “In Case of Fire Use Stairs” is not located on all landings. Install signage that conforms to the building code this elevator was installed to meet. | 6/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 6/18/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 6/25/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide MCP. | 6/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | 10/7/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch. | 10/7/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 6/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Hoistway door retainers are missing from all hoistway doors, need to install retainers. Re-inspection required |