Inspection
Inspection Details
Equipment ID
17311
17311
Inspection Date
10/16/2020
10/16/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Benjamin Postawko
Benjamin Postawko
Relief Valve Pressure
Slide
8"
8"
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
90fc6ee2-e8d9-4c98-8e84-eb921df6d287
90fc6ee2-e8d9-4c98-8e84-eb921df6d287
Location
Harrahs Casino
784 Casino Center Dr, Maryland Heights, MO
Phone: (314) 770-8278
784 Casino Center Dr, Maryland Heights, MO
Phone: (314) 770-8278
Owner
Attn: John Koshinski
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO 63043
Phone: (314) 770-8278
Email: John.Koshinski@pngaming.com
Hollywood Casino St. Louis
777 Casino Center Dr, Maryland Heights, MO 63043
Phone: (314) 770-8278
Email: John.Koshinski@pngaming.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Alarm bell shall work | 8/6/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Car door restrictor does not work. | 8/6/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Cab emergency lights do not work | 8/6/2018 |
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1001.2(e)(10) | Yes | Yes | Safety slide only 4", minimum slide 7". Repair and/or re-adjust safeties. Red tagged elevator. | 10/16/2020 |
| A17.1-2016 : Elevators | 3.16 - Traveling cables and junction boxes | 8.11.2.1.3(v) | No | No | Traveling cable insulation jacket is damaged. Repair or replace traveling cable. | 7/20/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/20/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Outer insulating jacket on traveling cable under car is coming off in several placed, no conductors exposed. Repair or replace | 11/1/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 11/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Traveling cable is damaged in several spots and needs to be replaced. Re-inspection required | 7/20/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/20/2026 |
| A17.1-2016 : Elevators | 3.16 - Traveling cables and junction boxes | 8.11.2.1.3(v) | Yes | No | Traveling cable is damaged in several spots and needs to be replaced. Re-inspection required |