Inspection
Inspection Details
Equipment ID
10970
10970
Inspection Date
11/2/2020
11/2/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vernon Livergood
Vernon Livergood
Mechanic Name
Dennis Smith
Dennis Smith
Relief Valve Pressure
Slide
00
00
Governor Rope Pull
000
000
Door Closing Force
27
27
External ID
bc3f1e89-f7f6-408a-82af-65bc4dd3fcd0
bc3f1e89-f7f6-408a-82af-65bc4dd3fcd0
Location
Kirkpatrick Building
620 FRANCIS ST, SAINT JOSEPH, MO
Phone: (816) 279-1010
620 FRANCIS ST, SAINT JOSEPH, MO
Phone: (816) 279-1010
Owner
St. John Holdings
117 S 7TH ST, SAINT JOSEPH, MO 64501-2229
117 S 7TH ST, SAINT JOSEPH, MO 64501-2229
Billing
Attn: Kirkpatrick Building
117 S 7TH ST, SAINT JOSEPH, MO 64501-2229
117 S 7TH ST, SAINT JOSEPH, MO 64501-2229
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Install permanent light fixture and switch in pit. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Pipes conveying liquids, vapors,gases not allowed in hoistway. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Install pit ladder with handrails extending 30 inches above landing | 7/15/2020 |
| conversion | conversion | n/a | No | No | Cover exposed motor leads in machine room. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Post current operating certificate. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Machine room door shall be self closing and self locking. | 7/15/2020 |
| conversion | conversion | n/a | No | No | No annual testing or inspection 2009 to 2001 and 2014 to 2017 per state website. No test tags on site for those years either. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Machine room fire extinguisher not certified. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Emergency light and bell do not operate. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Guard hoistway windows and mark HOISTWAY viewable from outside. | 7/15/2020 |
| conversion | conversion | n/a | No | No | Provide maintenance control plan | 7/15/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | PROVIDE A SELF CLOSING / SELF LOCKING MACHINE ROOM DOOR | 7/15/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | INSTALL A PIT LIGHT AND A GFCI OUTLET | 5/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | INSTALL A PIT LADDER | 5/9/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | THE INSTALLED PHONE IS NOT WORKING | 3/20/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | DISPLAY STATE OPERATING CERTIFICATE IN MACHINE ROOM | 5/9/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | PROVIDE A WORKING IN CAR EMERGENCY PHONE | 5/12/2025 |