Inspection Details
Equipment ID
4755
4755
Inspection Date
10/16/2020
10/16/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Zachary Thieme
Zachary Thieme
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
6652ca05-d3a1-4e2c-9c56-3d78a15c07bd
6652ca05-d3a1-4e2c-9c56-3d78a15c07bd
Location
MO Baptist Medical Center-Bldg C
3009 N BALLAS RD, SAINT LOUIS, MO
Phone: (314) 996-5346
3009 N BALLAS RD, SAINT LOUIS, MO
Phone: (314) 996-5346
Owner
Attn: UNK
BJC C/O Cushman And Wakefield Eager Rd
3009 N BALLAS RD, SAINT LOUIS, MO 63131
Phone: (000) 000-0000
Email: chelsey.housewright@cushwake.com
BJC C/O Cushman And Wakefield Eager Rd
3009 N BALLAS RD, SAINT LOUIS, MO 63131
Phone: (000) 000-0000
Email: chelsey.housewright@cushwake.com
Billing
Attn: BJC C/O Cushman And Wakefield Eager Rd
BJC C/O Cushman And Wakefield Eager Rd
8300 EAGER RD STE 600, SAINT LOUIS, MO 63144
Phone: (314) 996-5346
Email: chelsey.housewright@cushwake.com
BJC C/O Cushman And Wakefield Eager Rd
8300 EAGER RD STE 600, SAINT LOUIS, MO 63144
Phone: (314) 996-5346
Email: chelsey.housewright@cushwake.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | No | No | Bottom stop switch cover buzzer not working | 1/10/2020 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | No | No | Upper left handrail inlet guard needs to be replaced | 1/10/2020 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | No | No | lower left handrail inlet guard needs to be replaced | 1/10/2020 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | No | No | Bottom left lower balustrade gap exceeds maximum allowable | 1/10/2020 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | No | No | Demarcation lights not working | 1/10/2020 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | Yes | No | A17.2 - 7.17 - The step indexing loaded gap shall not be greater than 4.8mm on each side. | 9/10/2021 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | Yes | No | 8.6.8.3 - The step/skirt performance index shall not exceed .4. | 9/10/2021 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Top & bottom demarcation lamps shall be operational. | 9/10/2021 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Bottom demarcation lamps shall be operational. | 9/10/2021 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.6.2(i) Step Demarcation | Yes | No | The top and bottom demarcation lights shall be operational. | 10/6/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | Yes | No | The loaded step gap shall not exceed 4.8mm on either side. | 10/6/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.3 Step/Skirt Performance Index | Yes | No | The escalator step/skirt performance index shall not exceed .4. | 10/6/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.11.4.1(e) Lighting (demarcation and step lighting) | Yes | No | 8.6.11.6.2(i) Step Demarcation - The top and bottom demarcation lights shall be operational. (2nd Notice) | 5/19/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | Yes | No | The loaded step gap shall not exceed 4.8 mm on either side. (2nd Notice) | 5/19/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.3 Step/Skirt Performance Index | Yes | No | Performance index shall not exceed 0.4. (2nd Notice) | 5/19/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | Yes | No | Handrails will be free of major cracks and pinch points. Replace left handrail. | 5/19/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(B) | No | No | Replace damaged lower key up/down switch. | 5/19/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided. MCP shall be present and updated. | 5/19/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | No | No | Left handrail has excessive cracks. it must be replaced. (2nd notice) | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(B) | No | No | Missing step switch must be insalled at lower end. |