Inspection
Inspection Details
Equipment ID
15341
15341
Inspection Date
10/22/2020
10/22/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
18#
18#
External ID
96b3cd88-302c-4984-b82f-0058d1971ff8
96b3cd88-302c-4984-b82f-0058d1971ff8
Location
Windows On Washington-IBCI Bldg
1509 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 283-2331
1509 WASHINGTON AVE, SAINT LOUIS, MO
Phone: (314) 283-2331
Owner
Attn: Window On Washington-IBCI Bldg
IBC Investors LLC
PO BOX 5005, CAHOKIA, IL 62206-5005
IBC Investors LLC
PO BOX 5005, CAHOKIA, IL 62206-5005
Billing
Attn: IBC Investors LLC
Donny Choate
189 AMERICAN GRAIN ST, CAHOKIA, IL 62206-2938
Donny Choate
189 AMERICAN GRAIN ST, CAHOKIA, IL 62206-2938
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.12 | Yes | No | Remote governor trip not functioning. | 11/30/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | 9/10/2024 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | Provide Cat 5 testing of the car safeties. Record slide. Check rails for dressing. | 9/10/2024 |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 | No | No | Observed several bottom door guides (on different floors) don’t have fire tabs bent down, make so. | 4/7/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top. | 4/7/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean upper and lower pits. | 4/7/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2 through 2.27.8 Firefighter Service | Yes | Yes | On Phase II operations, door close function not working. Car removed from service. | 9/10/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | 4/7/2026 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | Provide Cat 5 safety test, record slide. | 4/7/2026 |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 | No | No | Observed bottom door guides ( on several floors) don’t have fire tabs bent down, make so. | 4/7/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. | 4/7/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean upper and lower pits. | 4/7/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communications/phone in car not working. | 5/5/2026 |